5276178-JIM-C-0118
FILTERS
Throwaway or rigid filters are supplied with each unit.
Filters must always be installed ahead of evaporator coil
and must be kept clean or replaced with same size and
type. Dirty filters will reduce the capacity of the unit and
will result in frosted coils or safety shutdown. Required
filter sizes are shown in Table 11. The unit should not
be operated without filters properly installed.
FIGURE 24 – DRAIN TRAP SHOWING WATER
LOCATION DURING DRAW
THROUGH OPERATION STAGES
LD06342-1
DRAIN
PAN
DRAIN
PAN
DRAIN
PAN
DRAIN
NIPPLE
TRAP
NO.1 - FAN OFF
NO. 2 - TRAP CONDITION WHEN FAN STARTS
NO. 3 - FAN RUNNING AND CONDENSATE
COOLING COIL
DRAIN PAN
CONDENSATE DRAIN
Condensate Drain Piping
The Series 40 cooling coils are located in the units so
that the supply air is drawn through them. This results
in the condensate being subjected to negative (-) static
pressure. Unless some means of pressure equalization
is provided in the condensate drain, the air rushing back
through the drainpipe will cause the condensate to build
up in the drain pan. As the unit continues to operate, the
accumulated water will be carried with the air stream,
overfilling the drain pan causing possible water leaks
into the supply duct and/or causing water damage in
the building. A trap must be installed to prevent this
condensate water build-up (
see Figures 19 and 20
).
LD14185
FIGURE 25 – RECCOMMENDED DRAIN
PIPING
Condensate Drain Trap
For
“Draw-through”
applications install a trapped
condensate drain line at unit drain connection (
see
Figure 25
) according to all governing codes. “H”
dimension must be at least 1/2 inch greater than design
Total Static Pressure (TSP) of fan.
The trap and drain lines should be protected from
freezing. Plumbing must conform to local codes. Use
a sealing compound on male pipe threads. Install
condensate drain lines from the 1-1/2 inch NPT female
connections on the unit to an open drain.
The unit must be properly trapped and
charged with water before the units
are started.
COMPRESSORS
Units are shipped with compressor mountings factory
adjusted and ready for operation.
DO NOT loosen compressor mount
-
ing bolts.
AIR HOODS
Air Hoods for Fixed Outside Air
(Units with Manual Economizer)
These hoods are factory installed. The dampers may
be adjusted by loosening the thumb screw, turning
the lever to the desired position, and retightening the
thumb screw.
Air Hoods for Economizer
There are three (3) economizer outside air intake hoods
provided with the unit. The hood on the end of the unit
is factory mounted. The two (2) front and rear hoods are
made operational per the following instructions.
Remove the screws holding the economizer hood
shipping covers in place. Discard covers.
Rotate the hoods out (each hood is hinged in the lower
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...