224
JOHNSON CONTROLS
5276178-JIM-C-0118
Parameter Description and Options
MENU ITEM
DEFINITION
OA DAMPER MINIMUM POSITION
This parameter is programmed through the SETPOINTS key. This establishes
the minimum amount of ventilation air to be used when the unit is in the Occupied
mode.
OA DAMPER POSITION ACTIVE SP
This is the damper position set point, in percent open, the Unit Controller is trying
to maintain.
OA DAMPER POSITION CURRENT
This is the actual output, in percent open to the outdoor air damper.
OAT SETPOINT FOR HIGH SAT
This parameter is programmed through the SETPOINTS key. When the outdoor
temperature is equal to or less than this temperature the Active Supply Air Temperature
Set Point on a Variable Air Volume Unit will be set to the SAT HIGH SETPOINT.
OAT SETPOINT FOR LOW SAT
This parameter is programmed through the SETPOINTS key. When the outdoor
temperature is equal to or greater than this temperature the Active Supply Air
Temperature Set Point on a Variable Air Volume Unit will be set to the SAT LOW
SETPOINT.
OUTSIDE AIR ENTHALPY
This indicates the total heat content of the outdoor air.
OUTSIDE AIR ENTHALPY SETPOINT
This parameter is programmed through the SETPOINTS key and is the upper limit
of outdoor enthalpy that can be used for economizer operation. If the outdoor air
enthalpy is above this value, the economizer is made inactive.
OUTSIDE AIR FLOW ACTIVE SP
This is the airflow set point that the Unit Controller is trying to maintain.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
OUTSIDE AIR FLOW TOTAL
This is the same as OA Flow 1 for a Minimum or Full IAQ and is the sum of the OA
Flow 1 and OA Flow 2 for a 1/3 - 2/3 IAQ.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
OUTSIDE AIR HUMIDITY
This is the outdoor air relative humidity.
OUTSIDE AIR MAXIMUM FLOW
This parameter is programmed through the SETPOINTS key. When air measurement
stations are installed and the unit is in the Demand Ventilation mode, this is the
maximum allowable airflow value.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
OUTSIDE AIR MINIMUM FLOW
This parameter is programmed through the SETPOINTS key. When air measurement
stations are installed and the unit is in the Demand Ventilation mode, this is the
minimum airflow value.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
OUTSIDE AIR TEMP
This is the outdoor air dry bulb temperature.
POWER EXHAUST TYPE
This parameter is programmed through the OPTIONS key and tells the Unit Controller
what type of Exhaust is installed. The choices are None, On-Off Damper Cntrl, On-Off
Press Cntrl, Modulate Damper VFD, Return Fan W/Exh, or Return Fan W/O Exh.
PRESS TRANS PKG
This parameter is programmed through the OPTIONS key. This identifies to the Unit
Controller which of the compressor systems are configured with suction and discharge
pressure transducers. The options are None, Sys 1; Sys 1, 2; or Sys 1, 2 and 3.
PRESSURE DISCHARGE*
This is the discharge pressure and is shown for each compressor system if pressure
transducers are installed and configured for the system.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
PRESSURE SUCTION*
This is the suction pressure and is shown for each compressor system if pressure
transducers are installed and configured for the system.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
TABLE 93
-
PARAMETER DEFINITIONS (CONT'D)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...