167
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 83 – SUPPLY SYSTEM
DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
SUPPLY SYS STATUS
NORMAL - ACTIVE
NORMAL - INACTIVE
SAFETY TRIP SAFETY
FAULT SAFETY
LOCKOUT
ALWAYS
SUPPLY FAN
OUTPUT
ON - OFF
DERIVED
ALWAYS
STATUS
RUNNING STOPPED
DERIVED
SUPPLY FAN VFD
SPEED
0.0 TO 100%
DERIVED
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
DUCT STATIC PRESS
CURRENT
0.00 TO 5.00 INWC
LOOK UP
TABLE
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
ACTIVE SP
0.00 TO 5.00 INWC
DERIVED
RETURN FAN
OUTPUT
ON - OFF
DERIVED
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
STATUS
RUNNING STOPPED
DERIVED
EXHAUST / RETURN
FAN VFD
0.0 TO 100%
DERIVED
POWER EXHAUST TYPE EQUALS
RETURN W/EXHAUST PLUS RETURN
W/O EXHAUST FANS
RETURN FAN PRESS
CURRENT
-1.00 TO +1.00 INWC
LOOK UP
TABLE
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
ACTIVE SP
0.00 TO +1.00 INWC
DERIVED
DUCT PRESS
TRANSDUCER SPAN
2
1.25, 2.5, 5.0
5.0
SETPOINTS /
SUPPLY SYSTEM
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
DUCT STATIC RESET
LOW SETP
1
0 - I IN-WG - SPAN
0 IN-WG TO DUCT
STATIC RESET HIGH
1.5 IN-WG
SETPOINTS /
SUPPLY SYSTEM
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
DUCT STATIC RESET
HIGH SETP
1
DUCT STATIC RESET
LOW LIMIT TO SPAN
2.5 IN-WG
SETPOINTS /
SUPPLY SYSTEM
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
DUCT STATIC OVER
PRESSURE
2
0 - I IN-WG - 5 IN-WG
3.0 IN-WG
SETPOINTS /
SUPPLY SYSTEM
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
FAN SPEED
INSTABILITY TIME
2
15 - 300 SEC
120 SEC
SETPOINTS /
SUPPLY SYSTEM
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
FAN SPEED
INSTABILITY LIMIT
2
10 - 50%
25%
SETPOINTS /
SUPPLY SYSTEM
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
INSTABILITY MONITOR
2
USER ENABLED
USER DISABLED
USER
DISABLED
PROGRAM /
SUPPLY SYSTEM
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
RETURN PRESSURE
HIGH SETP
2
0.15 TO 0.45
0.15
SETPOINTS /
SUPPLY SYSTEM
THIS FEATURE IS NOT
AVAILABLE ON THIS UNIT.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...