216
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 92 - N2 POINTS LIST (CONT'D)
(See notes at end of table)
B A C N E T
NAME
USER
I N T E R F A C E
NAME
READ/
WRITE
BACNET
OBJECT
TYPE
AND
INSTANCE
ENG
UNITS
N2
ADDRESS
POINTS LIST DESCRIPTION
TEMP_3_
SUCTION
TEMPERATURE 3
SUCTION
R
AI53
DEG F
AI 44
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
UND_FLR_
DEWP
UNDER FLOOR
DEW POINT
R
AI55
DEG F
AI 45
THE CALCULATED DEW POINT OF THE AIR UNDER
THE FLOOR IN A FLEXSYS SYSTEM (F)
UND_HUMD_
BAS
UNDER FLOOR
HUMIDITY BAS
R/W
AV36
%
AO 29
THIS ALLOWS THE BAS SYSTEM TO INPUT
A UNDER FLOOR HUMIDITY VALUE TO THE
CONTROL ON A FLEXSYS SYSTEM (%) “UNDER
FLR HUMI BAS” MUST BE ENABLED USING THE
SERVICE KEY IN ORDER TO USE THIS FEATURE
UND_FLR_
HUMD
UNDER FLOOR
HUMIDITY
R
AI56
%
AI 46
HUMIDITY VALUE OF THE AIR UNDER THE FLOOR
THE CONTROL IS CONTROLLING TO IN A FLEXSYS
SYSTEM (%)
UND_TEMP_
BAS
UNDER FLOOR
TEMP BAS
R/W
AV37
DEG F
AO 30
THIS ALLOWS THE BAS SYSTEM TO INPUT A
UNDER FLOOR TEMPERATURE VALUE TO THE
CONTROL ON A FLEXSYS SYSTEM (F). “UNDER
FLR TEMP BAS” MUST BE ENABLED USING THE
SERVICE KEY IN ORDER TO USE THIS FEATURE
UND_FLR_
TEMP
UNDER FLOOR
TEMP
R
AI57
DEG F
AI 47
TEMPERATURE OF THE AIR UNDER THE FLOOR
THE CONTROL IS CONTROLLING TO IN A FLEXSYS
SYSTEM (F)
UNIT_MODE
UNIT MODE
R
AI58
INDEX
AI 48
0 - OCCUPIED COOLING
1 - OCCUPIED COOLING LOW
2 - OCCUPIED COOLING HIGH
3 - OCCUPIED COOLING WITH BYPASS
4 - OCCUPIED COOLING WITHOUT BYPASS
5 - OCCUPIED HEATING
6 - OCCUPIED HEATING LOW
7 - OCCUPIED HEATING HIGH
8 - OCCUPIED STANDBY
9 - UNOCCUPIED COOLING
10 - UNOCCUPIED COOLING LOW
11 - UNOCCUPIED COOLING HIGH
12 - UNOCCUPIED HEATING
13 - UNOCCUPIED HEATING LOW
14 - UNOCCUPIED HEATING HIGH
15 - UNOCCUPIED STANDBY
16 - COMFORT VENT COOLING
17 - COMFORT VENT HEATING
18 - NIGHT SET BACK
19 - MORNING WARM UP
20 - POWER UP STANDBY
UNIT_STOP
UNIT STOP
R/W
AV93
0, 1
AO 40
THIS COMMAND ALLOWS THE UNIT TO BE SHUT
DOWN THROUGH THE BAS SYSTEM (0 = NORMAL
OPERATION/ 1 = STOPPED
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...