223
JOHNSON CONTROLS
5276178-JIM-C-0118
7
* May be 1, 2, or 3
MENU ITEM
DEFINITION
HEATING SYSTEM TYPE
This parameter is programmed through the OPTIONS key. This parameter is used
to identify the type of heat installed in the unit. The options are None, Electric, Stage
Gas, Modulating Gas, Hot Water / Steam.
HW / STEAM FRZ STAT
This is the status of the hydronic heat freezestat. This is done through a Binary input
to the Unit Controller. The switch is closed for normal operation and opens on failure.
The User Interface will indicate OK or FAULTED.
HW / STEAM HEAT - VALVE POS
This is the output from the Unit Controller to the hydronic valve as percent open.
HW VALVE ACTION
This parameter is programmed through the PROGRAM key. This parameter controls
the output to the hydronic modulating valve. When the parameter is set to DIRECT
the output is 0 volts for OFF and 10 volts for full capacity. When the parameter is set
to REVERSE the output is 10 volts for OFF and 0 volts for full capacity.
IAQ DMPR AIR FLOWS OA FLOW 1
This is the airflow through a Minimum, Full, or the 1/3 section of a 1/3 - 2/3 IAQ.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
IAQ DMPR AIR FLOWS OA FLOW 2
This is the airflow through the 2/3 section of a 1/3 - 2/3 IAQ.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
INSTABILITY MONITOR
This parameter is programmed through the PROGRAM key. This is used when two
units are twinned together to reduce the number of compressor in operation during
an instability period. The choices are USER ENABLED or USER DISABLED.
MAXIMUM BYPASS
This parameter is programmed through the SETPOINTS key. It establishes the
maximum allowable position of the bypass damper in a FlexSys unit.
MECH CLG LOCKOUT TEMP
This parameter is programmed through the SETPOINTS key. When the outdoor
temperature is equal to or less than this temperature, the Unit Controller will prevent
the compressors from operating.
MINIMUM OA FLOW SETPOINT
This parameter is programmed through the SETPOINTS key. When air measurement
stations are installed and the unit is not in the Occupied mode, this is the minimum
allowable airflow.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
MORNING WARM UP
This parameter is programmed through the PROGRAM key. This tells the Unit
Controller if the Morning Warmup option is available or not. When it is programmed to
USER ENABLED, Morning Warm Up is available to be used. When it is programmed
to USER DISABLED, Morning Warm Up is unavailable.
MORNING WARM UP MAX TIME
This parameter is programmed through the SETPOINTS key. This value is the
maximum time the Unit Controller will allow for Morning Warm Up when the unit is
in the Adaptive Morning Warm Up mode. If the derived Morning Warm Up Opt Time
exceed this time the Morning Warm Up Max Time will be used.
MORNING WARM UP OPT TIME
This is the average of the previous three days Warm Up times plus 10 minutes. This
value will be used to determine the Morning Warm Up start time for the next day
when the unit is in the Adaptive Morning Warm Up mode.
MX SUPPLY AIR TEMP
This parameter is programmed through the SETPOINTS key. This becomes the
Active Supply Air Temperature Set Point for a FlexSys unit when it is in the Occupied
Cooling Without Bypass mode.
NIGHT SET BACK
This parameter is programmed through the PROGRAM key. This parameter
allows the user to enable or disable Night Set Back. If this parameter is disabled
Unoccupied Heating will not be available. The two parameters to choose from are
USER ENABLED or USER DISABLED.
OA DAMPER MAXIMUM POSITION
This parameter is programmed through the SETPOINTS key. This establishes the
maximum amount of ventilation air to be used in a Demand Ventilation situation.
TABLE 93
-
PARAMETER DEFINITIONS (CONT'D)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...