200
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
RDY_RUN_C3B
READY TO RUN
COMP 3B
R
BI45
1326
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RDY_STOP_C1A
READY TO STOP
COMP 1A
R
BI46
1327
IDENTIFIES IF COMPRESSOR 1 IS READY TO STOP
IF THE COMPRESSOR IS RUNNING (YES / NO)
RDY_STOP_C1B
READY TO STOP
COMP 1B
R
BI47
1328
IDENTIFIES IF COMPRESSOR 2 IS READY TO STOP
IF THE COMPRESSOR IS RUNNING (YES / NO)
RDY_STOP_C2A
READY TO STOP
COMP 2A
R
BI48
1329
IDENTIFIES IF COMPRESSOR 3 IS READY TO STOP
IF THE COMPORESSOR IS RUNNING (YES / NO)
RDY_STOP_C2B
READY TO STOP
COMP 2B
R
BI49
1330
IDENTIFIES IF COMPRESSOR 4 IS READY TO STOP
IF THE COMPRESSOR IS RUNNING (YES / NO)
RDY_STOP_C3A
READY TO STOP
COMP 3A
R
BI50
1331
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RDY_STOP_C3B
READY TO STOP
COMP 3B
R
BI51
1332
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RET_AIR_BY_S
ACTIVE BYPASS
ACTIVE SP
R
AI37
550
A DERIVED VALUE FOR THE CURRENT SET POINT
OF THE RETURN AIR BYPASS DAMPER ON A
FLEXSYS UNIT (%)
RET_AIR_ENTH
RETURN AIR
ENTHALPY
R
AI38
551
ACTUAL RETURN AIR ENTHALPY (BTU/LB)
RET_AIR_HUMD
RETURN AIR
HUMIDITY
R
AI39
552
ACTUAL RETURN AIR RELATIVE HUMIDITY (%)
RET_AIR_TEMP
RETURN AIR TEMP
R
AI40
553
ACTUAL RETURN AIR TEMPERATURE (F)
RET_FAN_OUT
EXHAUST/RETURN
FAN VFD
R
AI41
554
THE OUTPUT FROM THE CONTROL TO THE
EXHAUST OR RETURN FAN VFD (%)
RET_FAN_PRES
RETURN FAN
PRESSURE
R
AI42
555
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RET_FAN_STAT
RETURN FAN
STATUS
R
BI52
1333
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
SAT_HIGH_LIM
SAT HIGH LIMIT
R/W
AV26
1051
THE UPPER LIMIT FOR THE SUPPLY AIR
TEMPERATURE SET POINT ON A VAV UNIT (F)
SAT_LOW_LIM
SAT LOW LIMIT
R/W
AV27
1052
THE LOWER LIMIT FOR THE SUPPLY AIR
TEMPERATURE SET POINT ON A VAV UNIT (F)
SAT_RST_BAS
SUPPLY AIR TEMP
RST BAS
R/W
AV28
1053
THIS IS AN ANALOG INPUT FROM THE BAS SYSTEM
THAT ALLOWS THE RESET OF THE ACTIVE SUPPLY
AIR TEMPERATURE SET POINT ON VAV UNITS. 0
VOLTS USES SAT HIGH LIMIT AND 5 VOLTS USES
SAT LOW LIMIT (V). “SAT RST BAS” MUST BE
ENABLED USING THE SERVICE KEY IN ORDER TO
USE THIS FEATURE
SAT_SUC_TMP1
SATURATED
SUCTION TEMP
(TEMPERATURES 1
SUCTION)
R
AI43
556
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
SAT_SUC_TMP2
SATURATED
SUCTION TEMP
(TEMPERATURES 2
SUCTION)
R
AI44
557
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
SAT_SUC_TMP3
SATURATED
SUCTION TEMP
(TEMPERATURES 3
SUCTION)
R
AI45
558
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...