MENU ITEM
DEFINITION
ECONO SYS STATUS
This is the active status of the economizer system; display will show Normal- Active,
Normal-Inactive, Faulted, User Disabled; or None.
ECONOMIZER CONTROL OUTPUT
This is the analog output from the Unit Controller to the Economizer Damper
Actuator.
ELEC HEAT CAPACITY
This parameter is programmed through the OPTIONS key. This parameter is used
to identify the electric heat capacity installed in the unit. The options are 40 KW, 80
KW, 40 KW-200, 80 KW-200, 100 KW, 100 KW-200, 108 KW, 120 KW, 150 KW, 160
KW, 200 KW, 240 KW, or 250 KW.
EVAP LEAVING AIR TEMP HIGH
This parameter is programmed through the SETPOINTS key. This becomes the
Active Supply Air Temperature Set Point for a FlexSys unit when it is in the Occupied
Cooling With Bypass mode.
EVAP LEAVING AIR TEMP LOW
This parameter is programmed through the SETPOINTS key. This becomes the
Active Supply Air Temperature Set Point for a FlexSys unit when it is in the Dew
Point Reset mode.
EXHAUST DAMPER POSITION
This identifies the percentage output from the Unit Controller to the exhaust
damper.
EXHAUST FAN OUTPUT
This identifies the Unit Controller is sending a Binary output to energize the exhaust
fan circuit.
EXHAUST FAN STATUS
This verifies a Binary input to the Unit Controller is present when the exhaust fan is
operating.
EXHAUST OUTPUT FOR FAN START
This parameter is set through the SETPOINTS key and identifies the position of the
exhaust damper required to turn ON the exhaust fan in an ON/OFF PRESS CNTRL
option.
EXHAUST OUTPUT FOR FAN STOP
This parameter is set through the SETPOINTS key and identifies the position of
the exhaust damper required to turn OFF the exhaust fan in an ON/OFF PRESS
CNTRL option.
EXHAUST SYS STATUS
This is the active status of the exhaust system. The display will show Normal-Active,
Normal-Inactive, Faulted, User Disabled, or None.
EXHAUST/RETURN FAN VFD
This is a derived value that indicates the output, in percent, to the Return Fan
VFD.
EXHAUST/RETURN FAN VFD
This identifies speed output in percentage that is being sent to the exhaust or return
fan VFD.
FAN SPEED INSTABILITY LIMIT
This parameter is programmed through the SETPOINTS key. If two units are twinned
together and the second unit comes ON there could be a sudden drop in VFD speed
on the lead unit. This is the allowable drop in the VFD speed in percent prior to
switching into a Unstable System mode.
FAN SPEED INSTABILITY TIME
This parameter is programmed through the SETPOINTS key. If two units are twinned
together and the second unit comes ON there could be a sudden drop in VFD speed
on the lead unit. This is the amount of time the lead unit has to recover prior to
switching into a Unstable System mode.
FAN SPEED SETP FOR HIGH SAT
This parameter is programmed through the SETPOINTS key. When the supply fan
speed is equal to or less than this value the Active Supply Air Temperature Set Point
on a Variable Air Volume Unit will be set to the SAT Set Point High Limit.
FAN SPEED SETP FOR LOW SAT
This parameter is programmed through the SETPOINTS key. When the supply fan
speed is equal to or greater than this value the Active Supply Air Temperature Set
Point on a Variable Air Volume Unit will be set to the SAT Set Point Low Limit.
TABLE 93
-
PARAMETER DEFINITIONS (CONT'D)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...