TABLE 92 - N2 POINTS LIST (CONT'D)
(See notes at end of table)
B A C N E T
NAME
USER
I N T E R F A C E
NAME
READ/
WRITE
BACNET
OBJECT
TYPE
AND
INSTANCE
ENG
UNITS
N2
ADDRESS
POINTS LIST DESCRIPTION
SAT_SUC_
TMP2
SATURATED
SUCTION TEMP
(TEMPERATURES
2 SUCTION)
R
AI44
DEG F
AI 37
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
SAT_SUC_
TMP3
SATURATED
SUCTION TEMP
(TEMPERATURES
3 SUCTION)
R
AI45
DEG F
AI 38
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
SEN_MSC_FLT
SENSOR/MISC
FAULT
R
BI54
0, 1
DI 20
IDENTIFIES IF A SENSOR OR MISCELLANEOUS
FAULT IS PRESENT (0 - NO FAULT; 1 - FAULTED)
SF_PROV_SW
SF PROVING
SWITCH
R
BI55
0, 1
DI 21
THE STATUS OF THE SUPPLY FAN AIR PROVING
CIRCUIT (0 - VERIFICATION CIRCUIT OPEN / 1 -
VERIFICATION CIRCUIT CLOSED)
STG_1_COOL
STG 1 COOLING
R/W
AV31
DEG F
AO 24
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A FIRST STAGE
COOLING DEMAND (F)
STG_1_HEAT
STG 1 HEATING
R/W
AV32
DEG F
AO 25
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A FIRST STAGE
HEATING DEMAND (F)
STG_2_COOL
STG 2 COOLING
R/W
AV33
DEG F
AO 26
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A SECOND STAGE
COOLING DEMAND (F)
STG_2_HEAT
STG 2 HEATING
R/W
AV34
DEG F
AO 27
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A SECOND STAGE
HEATING DEMAND (F)
SUP_AIR_
TEMP
SUPPLY AIR TEMP
R
AI46
DEG F
AI 39
ACTUAL SUPPLY AIR TEMPERATURE (F)
SUP_AIR_
TRST
SUPPLY AIR TEMP
RST
R
AI47
VDC
AI 40
THIS IS EITHER A HARDWIRED OR
COMMUNICATED 0 TO 5VDC INPUT THAT ADJUST
THE SUPPLY AIR SET POINT BETWEEN THE SAT
LOW AND SAT HIGH LIMIT (V)
SUP_FAN_VFD SUPPLY FAN VFD
R
AI48
%
AI 41
THE ACTUAL OUTPUT TO THE SUPPLY FAN VFD
(%)
SUPPLY_FAN
SUPPLY FAN
R
BI59
0, 1
DI 22
THE STATUS OF THE BINARY OUTPUT FROM THE
CONTROLLER TO THE SUPPLY FAN CIRCUIT (0 =
OFF, 1 = ON)
SYSTEM_STOP SYSTEM STOP
R/W
AV35
INDEX
AO 28
A 0- VALUE ALLOWS ALL COMPRESSORS TO
OPERATE; 1 - TURNS OFF COMPRESSOR SYSTEM
1; 2 - TURNS OFF COMPRESSOR SYSTEM 2; 3 -
TURNS OFF COMPRESSOR SYSTEM 3
TEMP_1_
SUCTION
TEMPERATURE 1
SUCTION
R
AI49
DEG F
AI 42
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
TEMP_2_
SUCTION
TEMPERATURE 2
SUCTION
R
AI51
DEG F
AI 43
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...