190
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
The data following the initial History Fault display is
displayed in the same order and with the same message
used under the respective menu function:
•
Status
•
Unit Data
•
Cooling
•
Supply System
•
Comp Sys 1
•
Comp Sys 2
•
Comp Sys 3
•
Heating
•
Economizer
•
Ventilation
•
Exhaust
•
Hours/Starts
Pressing the ▼ key from a History Fault display changes
the display to the History Section display format. The
► and ◄ keys are used to select a section. Pressing the
History or
X
key returns to the History Fault display.
Pressing the ▼ key displays the next parameter in the
selected list. From a parameter display, pressing the
History or
X
key returns to the History Fault display.
See Section 6 “Navigation Keys” for instructions for
navigating the parameter display.
For the following example, assume that there were three
faults and one warning logged.
First, the HISTORY key is pressed to get the password
prompt. If a level 2 password is active, this prompt is
skipped.
After entering the Level 2 password, the most recent
WARNING is displayed.
The ► key is pressed to move to the first fault.
The ► key is pressed to move to the next older fault
(fault # 2).
The ► key is pressed to move to the next older fault
(fault # 3).
The ▼ key is pressed to view data saved when fault
#3 was detected.
The ▼ key is pressed to view the second STATUS
value.
The ► key is pressed to change to the next data section
(UNIT DATA).
The
X
or HISTORY key is pressed to go back to the
fault display.
HISTORY
ENTER PASSWORD
HISTORY WARNING
◄►
+ WRN-BUILDING PRS
HISTORY 01 31 OCT 2004 12:45:59 AM
◄►
+ LOCKOUT-DUCT PRS XDCR
HISTORY 02 31 OCT 2004 10:42:39 AM
◄►
AUTO RESET-MSAT SENSOR
HISTORY 03 30 OCT 2004 02:11:23 PM
◄►
WRN-BUILDING PRS
HISTORY 03 – STATUS
◄►
UNIT-OVERALL STATUS RUN
HISTORY 03 – STATUS
◄►
CURRENT OPER MODE RUN
HISTORY 03 – UNIT DATA
◄►
UNIT TYPE CONSTANT VOLUME
HISTORY 03 30 OCT 2004 02:11:23 PM
◄►
WRN-BUILDING PRS
From fault display, the
X
key can be pressed to return
to the Power Up Banner display.
PASSWORD
Passwords are used to allow restricted access to the
modification and viewing of certain parameters using
the SETPOINTS, PROGRAM, OPTIONS, DATE/
TIME, SCHEDULE, OPERATING HOURS / START
COUNTER, PRINT, SERVICE, and HISTORY menu
keys. The menus activated by each of these buttons can
only be viewed after an acceptable password is entered.
Each parameter is associated with a level of access. Each
level of access is associated with a specific password.
The access levels available are: Level 1 or Level 2.
•
If a parameter is tagged as Level 1, password
of 9675 must be entered in order to change the
value.
•
If a parameter is tagged as Level 2, a password
of 9725 must be entered in order to change the
value. Entering the Level 2 password will also
allow the changing of a Level 1 parameter.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...