73
2
JOHNSON CONTROLS
5276178-JIM-C-0118
Table 34 Electrical Data 40 Ton 208/230 Volt WITHOUT ERV (Cont.)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Heat Option
Conv
Outlet
Supply
Blower
Motor
Pwr
Exh
Motor
W/O Pwrd Conv
Outlet
With Pwrd Conv
Outlet
MCA
1
Max
Fuse
2
/
Breaker
3
Size
MCA
1
Max
Fuse
2
/
Breaker
3
Size
QTY RLA LRA MCC
FLA
Model kW
Stages Amps
FLA
HP FLA HP
FLA
Amps
Amps
Amps
Amps
208-3-60
4
28.2
240
44
5.8
E8
60.1
2
167
11.5
10
30.8
-
-
206
225
217
225
7.5
24.2
230
250
241
250
10
30.8
236
250
248
250
15
46.2
256
300
267
300
15
46.2
-
-
225
250
236
250
7.5
24.2
249
250
260
300
10
30.8
256
300
267
300
15
46.2
271
300
282
300
20
59.4
-
-
241
300
253
300
7.5
24.2
265
300
277
300
10
30.8
272
300
284
300
15
46.2
287
300
299
350
25
74.8
-
-
261
300
272
300
7.5
24.2
285
350
296
350
10
30.8
291
350
303
350
15
46.2
307
350
318
350
230-3-60
4
28.2
240
44
5.8
E8
80
2
185
10.4
10
28
-
-
220
250
230
250
7.5
22
242
250
252
300
10
28
248
250
258
300
15
42
266
300
276
300
15
42
-
-
238
250
248
250
7.5
22
260
300
270
300
10
28
266
300
276
300
15
42
280
300
290
300
20
54
-
-
253
300
263
300
7.5
22
275
300
285
300
10
28
281
300
291
300
15
42
295
300
305
350
25
68
-
-
270
300
280
300
7.5
22
292
350
302
350
10
28
298
350
308
350
15
42
312
350
322
350
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...