User Interface Control Center
TABLE 90
-
LON POINTS LIST
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
W2_HIGH_HEAT
W2 HIGH HEAT
R
BI63
1344
IDENTIFIES THE STATUS OF THE W2 HEAT INPUT
WITH EITHER A HARDWIRED OR COMMUNCIATED
INPUT (ON / OFF)
Y1_LO_COOL_B
Y1 LOW COOL BAS
R/W
AV(BV)98
1123
A COMMUNICATED VALUE THAT ALLOWS THE Y1
COOL CALL TO BE TURNED ON AND OFF (0 = OFF;
1 = ON)
Y1_LOW_COOL
Y1 LOW COOL
R
BI64
1345
IDENTIFIES THE STATUS OF THE Y1 COOL INPUT
WITH EITHER A HARDWIRED OR COMMUNCIATED
INPUT (ON / OFF)
Y2_HI_COOL_B
Y2 HIGH COOL
BAS
R/W
AV(BV)99
1124
A COMMUNICATED VALUE THAT ALLOWS THE Y2
COOL CALL TO BE TURNED ON AND OFF (0 = OFF;
1 = ON)
Y2_HIGH_COOL
Y2 LOW COOL
R
BI65
1346
IDENTIFIES THE STATUS OF THE Y2 COOL INPUT
WITH EITHER A HARDWIRED OR COMMUNCIATED
INPUT (ON / OFF)
ZONE_TEMP
ZONE TEMP
R
AI60
573
ZONE TEMPERATURE THE CONTROL IS
CONTROLLING TO (F)
ZONE_TMP_BAS
ZONE TEMP BAS
R/W
AV40
1065
THIS ALLOWS THE BAS SYSTEM TO INPUT A
ZONE TEMPERATURE VALUE, DEGREE F, TO THE
CONTROL. TO USE THIS FEATURE THE “CONTROL
METHOD” MUST BE SET TO “COMM ZONE TEMP”
Notes:
1. The most up to date listing of the Standard Points Mapping can be found in the Johnson Controls website.
2. In order to do BACnet IP a gateway model FS-B2010-02-01Y must be purchased from fieldserver technologies.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...