105
3
JOHNSON CONTROLS
5276178-JIM-C-0118
TABLE 61 - WATER PRESSURE DROP (2 ROW, 25 & 30 TON)
GPM
20
40
60
80
WATER PRESSURE DROP
0.9
3.0
6.0
10.0
TABLE 62 - WATER PRESSURE DROP (2 ROW, 40 TON)
GPM
20
40
60
80
WATER PRESSURE DROP
0.9
3.0
6.0
10.0
TABLE 63 - STATIC RESISTANCE HOT WATER COIL (25 & 30 TON)
CFM
6000
8000
10000
15000
AIR PRESSURE DROP 1 ROW
0.07
0.11
0.16
0.32
AIR PRESSURE DROP 2 ROW
0.14
0.23
0.33
0.65
TABLE 64 - STATIC RESISTANCE HOT WATER COIL (40 TON)
CFM
80000
11000
14000
20000
AIR PRESSURE DROP 1 ROW
0.11
0.19
0.29
0.52
AIR PRESSURE DROP 2 ROW
0.23
0.39
0.58
1.06
NOTE: Water pressure drop numbers are based on 60°F entering air temperature, 2.00” maximum air pressure drop across the hot water
coil(s). ARI certified ratings at covering other conditions are available upon request. Hot water coils are approved for use with glycol (rates
available upon request).