TABLE 91 - LON POINTS LIST (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
BACnet
OBJECT
TYPE
AND IN-
STANCE
SNVT
POINTS LIST DESCRIPTION
nvoUNIT_MODE
UNIT MODE
AI-058
SNVT_count
(8)
0 - OCCUPIED COOLING
1 - OCCUPIED COOLING LOW
2 - OCCUPIED COOLING HIGH
3 - OCCUPIED COOLING WITH BYPASS
4 - OCCUPIED COOLING WITHOUT BYPASS
5 - OCCUPIED HEATING
6 - OCCUPIED HEATING LOW
7 - OCCUPIED HEATING HIGH
8 - OCCUPIED STANDBY
9 - UNOCCUPIED COOLING
10 - UNOCCUPIED COOLING LOW
11 - UNOCCUPIED COOLING HIGH
12 - UNOCCUPIED HEATING
13 - UNOCCUPIED HEATING LOW
14 - UNOCCUPIED HEATING HIGH
15 - UNOCCUPIED STANDBY
16 - COMFORT VENT COOLING
17 - COMFORT VENT HEATING
18 - NIGHT SET BACK
19 - MORNING WARM UP
20 - POWER UP STANDBY
nviUNIT_STOP
UNIT STOP
AV-093
SNVT_switch
(95)
THIS COMMAND ALLOWS THE UNIT TO BE SHUT DOWN
THROUGH THE BAS SYSTEM (0 = NORMAL OPERATION/ 1 =
STOPPED
nviUNOCC_ZN_COOL
UNOCCUPIED
ZONE COOLING
AV-038
SNVT_count_f
(51)
THE UNOCCUPIED ZONE COOLING SET POINT (F)
nviUNOCC_ZN_HEAT
UNOCCUPIED
ZONE HEATING
AV-039
SNVT_count_f
(51)
THE UNOCCUPIED ZONE HEATING SET POINT (F)
nvoUNSTABLE _SYS
UNSTABLE
SYSTEM
BI-060
SNVT_switch
(95)
THIS INDICATES A UNSTABLE SYSTEM WHEN TWO UNITS
ARE TWINNED TOGETHER AND THERE IS A SUDDEN DROP IN
SUPPLY AIR TEMPERATURE OR FAN SPEED (YES - UNSTABLE
CONDITION / NO - NORMAL OPERATION)
nvoVENT_DEM_OUT
VENTILATION
DEMAND P1 OUTP
AI-059
SNVT_switch
(95)
THE VENTILATION OUTPUT BEING GENERATED BY THE DE-
MAND VENTILATION FEATURE (%)
nviVENT_ENABLE
VENTILATION EN-
ABLE
AV-095
SNVT_switch
(95)
THIS COMMAND ALLOWS THE VENTILATION FUNCTION TO BE
TURNED ON OR OFF (0 = OFF / 1 = ON)
nviZONE_TMP_BAS
ZONE TEMP BAS
AV-040
SNVT_count_f
(51)
THIS ALLOWS THE BAS SYSTEM TO INPUT A ZONE TEMPERA-
TURE VALUE TO THE CONTROL ON A CONSTANT VOLUME UNIT
WITH COMMUNICATED ZONE CONTROL (F)
nvoZONE_TEMP
ZONE TEMP
AI-060
SNVT_count_f
(51)
ZONE TEMPERATURE THE CONTROL IS CONTROLLING TO (F)
Notes:
1. The most up to listing of the Standard Points Mapping can be found in the Johnson Controls website
2. In order to do LON protocol a e-link gateway part number YK-ELNK101-0 or YK-ELNKE01-0 must be used
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...