JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 92 - N2 POINTS LIST (CONT'D)
(See notes at end of table)
B A C N E T
NAME
USER
I N T E R F A C E
NAME
READ/
WRITE
BACNET
OBJECT
TYPE
AND
INSTANCE
ENG
UNITS
N2
ADDRESS
POINTS LIST DESCRIPTION
PRS_2_DISCH
PRESSURES 2
DISCHARGE
R
AI33
PSI
AI 26
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_2_
SUCTION
PRESSURES 2
SUCTION
R
AI34
PSI
AI 27
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_3_DISCH
PRESSURES 3
DISCHARGE
R
AI35
PSI
AI 28
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
PRS_3_
SUCTION
PRESSURES 3
SUCTION
R
AI36
PSI
AI 29
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RAT_COOL_SP
RAT COOLING
SETP
R/W
AV23
DEG F
AO 20
ON A VAV OR FLEXSYS UNIT THIS VALUE IS USED
TO DETERMINE WHEN THE UNIT SHOULD SWITCH
TO THE COOLING MODE (F)
RET_AIR_BY_S
ACTIVE BYPASS
ACTIVE SP
R
AI37
%
AI 30
A DERIVED VALUE FOR THE CURRENT SET POINT
OF THE RETURN AIR BYPASS DAMPER ON A
FLEXSYS UNIT (%)
RET_AIR_
ENTH
RETURN AIR
ENTHALPY
R
AI38
BTU/LB
AI 31
ACTUAL RETURN AIR ENTHALPY (BTU/LB)
RET_AIR_
HUMD
RETURN AIR
HUMIDITY
R
AI39
%
AI 32
ACTUAL RETURN AIR RELATIVE HUMIDITY (%)
RET_AIR_
TEMP
RETURN AIR
TEMP
R
AI40
DEG F
AI 33
ACTUAL RETURN AIR TEMPERATURE (F)
RET_FAN_OUT
EXHAUST/
RETURN FAN VFD
R
AI41
%
AI 34
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RET_FAN_
PRES
RETURN FAN
PRESSURE
R
AI42
WC
AI 35
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
RET_FAN_
STAT
RETURN FAN
STATUS
R
BI52
0, 1
DI 19
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
SAT_HIGH_LIM SAT HIGH LIMIT
R/W
AV26
DEG F
AO 21
THE UPPER LIMIT FOR THE SUPPLY AIR
TEMPERATURE SET POINT ON A VAV UNIT (F)
SAT_LOW_LIM SAT LOW LIMIT
R/W
AV27
DEG F
AO 22
THE LOWER LIMIT FOR THE SUPPLY AIR
TEMPERATURE SET POINT ON A VAV UNIT (F)
SAT_RST_BAS
SUPPLY AIR TEMP
RST BAS
R/W
AV28
VDC
AO 23
THIS IS AN ANALOG INPUT FROM THE BAS
SYSTEM THAT ALLOWS THE RESET OF THE
ACTIVE SUPPLY AIR TEMPERATURE SET POINT
ON VAV UNITS. 0 VOLTS USES SAT HIGH LIMIT
AND 5 VOLTS USES SAT LOW LIMIT (V). “SAT RST
BAS” MUST BE ENABLED USING THE SERVICE
KEY IN ORDER TO USE THIS FEATURE
SAT_SUC_
TMP1
SATURATED
SUCTION TEMP
(TEMPERATURES
1 SUCTION)
R
AI43
DEG F
AI 36
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...