TABLE 91
-
LON POINTS LIST (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
BACnet
OBJECT
TYPE
AND IN-
STANCE
SNVT
POINTS LIST DESCRIPTION
nvoDCT_ST_PR_RT
DUCT STATIC
PRES RST
AI-016
SNVT_switch
(95)
A HARDWIRED ENTERED ANALOG VOLTAGE THAT RESULTS IN
A %RESET DOWN FROM THE DUCT STATIC HIGH LIMIT BASED
ON A PERCENT OF THE DIFRFERENCE BETWEEN DUCT STATIC
HIGH LIMIT AND DUCT STATIC LOW LIMIT (%)
nvoDCT_STAT_PRS
DUCT STATIC
PRES
AI-017
SNVT_count_f
(51)
ACTUAL DUCT STATIC PRESSURE INPUT TO THE CONTROL
("WG)
nviDEW_PNT_RST
DEW POINT RESET
AV-080
SNVT_switch
(95)
THIS ALLOWS THE DEW POINT RESET FEATURE TO BE
TURNED ON AND OFF ON FLEXSYS UNITS (0 = OFF / 1 = ON)
nviDSP_HI_LIMIT
DUCT STATIC HIGH
LIMIT
AV-003
SNVT_count_f
(51)
THE DUCT STATIC UPPER SET POINT ("WG)
nviDSP_LO_LIMIT
DUCT STATIC LOW
LIMIT
AV-004
SNVT_count_f
(51)
THE DUCT STATIC LOWER SET POINT ("WG)
nviDSP_RST_BAS
DUCT STATIC
PRES RST BAS
AV-005
SNVT_switch
(95)
A BAS ENTERED VALUE THAT RESULTS IN A %RESET DOWN
FROM THE DUCT STATIC HIGH LIMIT BASED ON A PERCENT OF
THE DIFRFERENCE BETWEEN DUCT STATIC HIGH LIMIT AND
DUCT STATIC LOW LIMIT (%). "DUCT PRES RST BAS" MUST BE
ENABLED USING THE SERVICE KEY IN ORDER TO USE THIS
FEATURE
nviECONO_INSTAL
ECONOMIZER
INSTALLED
AV-081
SNVT_switch
(95)
ALLOWS THE ECONOMIZER FEATURE TO BE TURNED ON AND
OFF (0 = OFF / 1 = ON)
nvoECON_ME_USED
ECONOMIZER
METHOD
AI-018
SNVT_count
(8)
THE ECONOMIZER METHOD BEING USED BY THE CONTROL
(1 - DRY BULB; 2 - SINGLE ENTHALPY; 3 - DUAL ENTHALPY; 4 -
BEST METHOD)
nvoECON_STATUS
ECONOMIZER
SUITABLE ECON
INSTALLED
AI-019
SNVT_count
(8)
STATUS OF THE ECONOMIZER OPTION (0 - INSTALLED AND
INACTIVE; 1 - INSTALLED AND ACTIVE; 2 - NOT INSTALLED; 3 -
DISABLED)
nviEL_AIR_TMP_H
EVAP LEAVING AIR
TEMP HIGH
AV-007
SNVT_count_f
(51)
ON A FLEXSYS UNIT WITH BYPASS THIS IS THE SUPPLY AIR
TEMPERATURE HIGH SET POINT (F)
nviEL_AIR_TMP_L
EVAP LEAVING AIR
TEMP LOW
AV-008
SNVT_count_f
(51)
ON A FLEXSYS UNIT WITH BYPASS THIS IS THE SUPPLY AIR
TEMPERATURE LOW SET POINT (F)
nvoEVAP_AIR_TMP
EVAPORATOR AIR
TEMP 1
AI-020
SNVT_count_f
(51)
ACTUAL TEMPERATURE OF AIR LEAVING THE EVAPORATOR
COIL ON A FLEXSYS UNIT (F)
nvoEXHAUST_FAN
EXHAUST FAN
BI-022
SNVT_switch
(95)
THE STATUS OF THE BINARY OUTPUT FOR THE EXHAUST ( ON
/ OFF)
nvoEXH_FAN_STAT
EXHAUST FAN
STATUS
BI-021
SNVT_switch
(95)
THE STATUS OF THE EXHAUST FAN RUN VERIFICATION CIR
-
CUIT (RUN - ON VERIFICATION CIRCUIT CLOSED / STO - STOP
- VERIFICATION CIRCUIT OPEN)
nvoFAN_FAULT
FAN FAULT
BI-023
SNVT_switch
(95)
IDENTIFIES IF THERE IS A SUPPLY, EXHAUST, OR RETURN FAN
FAULT (0 - NO FAULT; 1= FAULTED)
nvoFILTER_STATS
FILTER STATUS
BI-025
SNVT_switch
(95)
IDENTIFIES THE STATUS OF THE BINARY DIRTY FILTER INPUT
(0- NO FAULT; 1- FAULTED)
nvoHEAT_ENT_TMP
HEAT ENTERING
TEMP
AI-022
SNVT_count_f
(51)
ACTUAL TEMPERATURE OF THE AIR ENTERING THE STAGGED
HEAT SECTION (F)
nviHEATING_SAT
HEATING SAT
AV-009
SNVT_count_f
(51)
THE HEATING SAT SET POINT FOR A VAV OR FLEXSYS UNIT (F)
nvoHEAT_STAGES
ELECTRIC HEAT
STAGES GAS HEAT
STAGES
AI-023
SNVT_count
(8)
DERIVED VALUE SHOWING THE NUMBER OF ELECTRIC OR
STAGGED GAS HEAT STAGES AVAILABLE (1 - 7)
nvoHEATING_VALV
HEATING VALVE
AI-024
SNVT_switch
(95)
THE OUPUIT FROM THE CONTROL TO A HOT WATER, STEAM,
OR MODULATING GAS HEAT VALVE (%)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...