201
JOHNSON CONTROLS
5276178-JIM-C-0118
6
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
SAT_TEMPER
SAT TEMPERING
ENABLE
R
BI53
1334
IDENTIFIES IF SUPPLY AIR TEMPERING IS TURNED
ON (ON / OFF)
SEN_MSC_FLT
SENSOR/MISC
FAULT
R
BI54
1335
IDENTIFIES IF A SENSOR OR MISCELLANEOUS
FAULT IS PRESENT (0 - NO FAULT; 1 - FAULTED)
SF_PROV_SW
SF PROVING
SWITCH
R
BI55
1336
THE STATUS OF THE SUPPLY FAN AIR PROVING
CIRCUIT ( STO - STOP VERIFICATION CIRCUIT
OPEN / 1 - RUN VERIFICATION CIRCUIT CLOSED)
SF_SPD_H_SAT
SF SPEED FOR
HIGH SAT
R/W
AV29
1054
THE FAN SPEED THE CONTROL USES WHEN
USING SUPPLY FAN SPEED SAT RESET TO SWITCH
TO THE SAT HIGH LIMIT SET POINT (%)
SF_SPD_L_SAT
SF SPEED FOR
LOW SAT
R/W
AV30
1055
THE FAN SPEED THE CONTROL USES WHEN
USING SUPPLY FAN SPEED SAT RESET TO SWITCH
TO THE SAT LOW LIMIT SET POINT (%)
SMOKE_PUR_1
SMOKE PURGE 1
R
BI56
1337
IDENTIFIES THE STATUS OF THE SMOKE PURGE 1
INPUT EITHER HARD WIRED OR COMMUNICATED
(ON / OFF)
SMOKE_PUR_2
SMOKE PURGE 2
R
BI57
1338
IDENTIFIES THE STATUS OF THE SMOKE PURGE 2
BINARY EITHER HARD WIRED OR COMMUNICATED
(ON / OFF)
SMOKE_PUR_3
SMOKE PURGE 3
R
BI58
1339
IDENTIFIES THE STATUS OF THE SMOKE PURGE 3
INPUT EITHER HARD WIRED OR COMMUNICATED
(ON / OFF)
SMOKE_PUR1_B
SMOKE PURGE 1
BAS
R/W
AV(BV)90
1115
A COMMUNICATED INPUT THAT ALLOWS SMOKE
PURGE 1 TO BE TURNED ON OR OFF (0 = OFF; 1 =
OFF)
SMOKE_PUR2_B
SMOKE PURGE 2
BAS
R/W
AV(BV)91
1116
A COMMUNICATED INPUT THAT ALLOWS SMOKE
PURGE 2 TO BE TURNED ON OR OFF (0 = OFF; 1 =
OFF)
SMOKE_PUR3_B
SMOKE PURGE 3
BAS
R/W
AV(BV)92
1117
A COMMUNICATED INPUT THAT ALLOWS SMOKE
PURGE 3 TO BE TURNED ON OR OFF (0 = OFF; 1 =
OFF)
STG_1_COOL
STG 1 COOLING
R/W
AV31
1056
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A FIRST STAGE
COOLING DEMAND (F)
STG_1_HEAT
STG 1 HEATING
R/W
AV32
1057
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A FIRST STAGE
HEATING DEMAND (F)
STG_2_COOL
STG 2 COOLING
R/W
AV33
1058
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A SECOND STAGE
COOLING DEMAND (F)
STG_2_HEAT
STG 2 HEATING
R/W
AV34
1059
FOR A CONSTANT VOLUME UNIT THIS IS THE
ACTIVE SAT SET POINT FOR A SECOND STAGE
HEATING DEMAND (F)
SUP_AIR_TEMP
SUPPLY AIR TEMP
R
AI46
559
ACTUAL SUPPLY AIR TEMPERATURE (F)
SUP_AIR_TRST
SUPPLY AIR TEMP
RST
R
AI47
560
THIS IS EITHER A HARDWIRED OR COMMUNICATED
0 TO 5VDC INPUT THAT ADJUST THE SUPPLY AIR
SET POINT BETWEEN THE SAT LOW AND SAT HIGH
LIMIT (V)
SUP_FAN_VFD
SUPPLY FAN VFD
R
AI48
561
THE ACTUAL OUTPUT TO THE SUPPLY FAN VFD (%)
SUPPLY_FAN
SUPPLY FAN
R
BI59
1340
THE STATUS OF THE BINARY OUTPUT FROM THE
CONTROLLER TO THE SUPPLY FAN CIRCUIT (0 =
OFF, 1 = ON)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...