95
3
JOHNSON CONTROLS
5276178-JIM-C-0118
TABLE 42 - 25 TON DRIVE ADJUSTMENT FOR CONSTANT VOLUME & VAV UNITS CLASS 1 & 2 FC FAN
7.5 HP MOTOR & 567 RPM DRIVE
10 HP MOTOR & 692 RPM DRIVE
15 HP MOTOR & 793 RPM DRIVE
20 HP MOTOR & 894 RPM DRIVE
%RPM
CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
% RPM
CFM
REQ’D
PD
BROWNING
2B5V_ _
-
-
-
82
4.5
42
84
5.3
50
86
6.1
58
-
-
-
86
4.7
44
87
5.5
52
89
6.3
60
100
(STD.)
4.5
1
42
89
4.9
46
90
5.7
54
91
6.5
62
104
4.7
44
93
5.1
48
94
5.9
56
94
6.7
64
109
4.9
46
96
5.3
50
97
6.1
58
97
6.9
66
113
5.1
48
100
(STD.)
5.5
1
52
100
(STD)
6.3
1
60
100
(STD.)
7.1
1
68
118
5.3
50
104
5.7
54
103
6.5
62
103
7.3
70
122
5.5
52
107
5.9
56
106
6.7
64
108
7.7
74
126
5.7
54
111
6.1
58
110
6.9
66
117
8.3
80
-
-
-
115
6.3
60
113
7.1
68
125
8.9
86
-
-
-
118
6.5
62
116
7.3
70
-
-
-
-
-
-
122
6.7
64
122
7.7
74
-
-
-
TABLE 43 - 30 TON DRIVE ADJUSTMENT FOR CONSTANT VOLUME & VAV UNITS CLASS 1 & 2 FC FAN
10 HP MOTOR & 617 RPM DRIVE
15 HP MOTOR & 743 RPM DRIVE
20 HP MOTOR & 856 RPM DRIVE
25 HP MOTOR & 907 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
91.8
4.5
42
86.4
5.1
48
82.1
5.5
54
86.3
6.1
60
95.9
4.7
44
89.8
5.3
50
85.1
5.7
56
89.0
6.3
62
100
(STD.)
4.9
1
46
93.2
5.5
52
88.1
5.9
58
91.8
6.5
64
104.1
5.1
48
96.6
5.7
54
91.0
6.1
60
94.5
6.7
66
108.2
5.3
50
100.0
(STD.)
5.9
1
56
94.0
6.3
62
97.3
6.9
68
112.2
5.5
52
103.4
6.1
58
97.0
6.5
64
100.0
(STD.)
7.1
1
70
116.3
5.7
54
106.8
6.3
60
100.0
(STD.)
6.7
1
66
105.5
7.5
74
120.4
5.9
56
110.2
6.5
62
103.0
6.9
68
113.7
8.1
80
124.5
6.1
58
113.6
6.7
64
106.0
7.1
70
121.9
8.7
86
-
-
-
116.9
6.9
66
112.0
7.5
74
-
-
-
-
-
-
120.3
7.1
68
120.9
8.1
80
-
-
-
-
-
-
123.7
7.3
70
129.9
8.7
86
-
-
-
DRIVE ADJUSTMENT TABLES
1. (STD), STANDARD FACTORY SUPPLIED DRIVE. ALL OTHER DRIVE COMBINATIONS MUST BE PURCHASED AND FIELD INSTALLED.
1. (STD), STANDARD FACTORY SUPPLIED DRIVE. ALL OTHER DRIVE COMBINATIONS MUST BE PURCHASED AND FIELD INSTALLED.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...