225
JOHNSON CONTROLS
5276178-JIM-C-0118
7
MENU ITEM
DEFINITION
PUMPDOWN
This parameter is programmed through the PROGRAM key. If Pumpdown is USER
ENABLED at the end of the compressor system cycle the solenoid value to the
expansion vales will close and the compressor will continue to operate for 30 seconds
or until the low pressure cutout opens. This removes the refrigerant from the low side
of the system. The choices are USER ENABLED or USER DISABLED. If Pumpdown
is ENABLED all compressor system will use Pumpdown.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
RAT COOLING SETPOINT
On a VAV or FlexSys unit, the Unit Controller monitors the RAT COOLING SETPOINT.
When the return air temperature is 0.5º F above this value the control switches into
the Occupied Cooling mode.
RAT HEATING SETPOINT
On a VAV or FlexSys unit, the Unit Controller monitors the RAT HEATING SETPOINT.
When the return air temperature is 0.5º F below this value the control switches into
the Occupied Heating mode.
RAT SETPOINT FOR HIGH SAT
This parameter is programmed through the SETPOINTS key. When the Return
Air Temperature is equal to or LESS than this temperature the Active Supply Air
Temperature Set Point on a Variable Air Volume Unit will be set to the SAT HIGH
SETPOINT.
RAT SETPOINT FOR LOW SAT
This parameter is programmed through the SETPOINTS key. When the Return
Air Temperature is equal to or greater than this temperature the Active Supply Air
Temperature Set Point on a Variable Air Volume Unit will be set to the SAT LOW
SETPOINT.
READY TO RUN COMP A
This means the minimum OFF time has been achieved and all the safety circuits
are closed and compressor 1 or 3 is ready to be energized. The User Interface will
display either YES or NO.
READY TO RUN COMP B
This means the minimum OFF time has been achieved and all the safety circuits
are closed and compressor 2 or 4 is ready to be energized. The User Interface will
display either YES or NO
READY TO STOP COMP A
This means the minimum ON time has been achieved and compressor 1 or 3 is ready
to be de-energized. The User Interface will display either YES or NO.
READY TO STOP COMP B
This means the minimum ON time has been achieved and compressor 2 or 4 is ready
to be de-energized. The User Interface will display either YES or NO.
REFRIGERANT TYPE
This parameter is programmed through the OPTIONS key and identifies the type of
refrigerant in the unit. The choices are R22, R407C, or R410A.
RETURN AIR BYPASS ACTIVE SP
This is the position of the bypass damper by percent open the Unit Controller uses
as the bypass set point on a FlexSys unit.
RETURN AIR BYPASS CURRENT
This is the position of the by-pass damper by percent open the Unit Controller uses
as the Active Bypass percent set point on a FlexSys unit.
RETURN AIR ENTHALPY
This is the total heat content of the return air.
RETURN AIR HUMIDITY
This is the return air relative humidity.
RETURN AIR TEMP
This is the return air dry bulb temperature.
RETURN AIR TEMP CURRENT
This is the temperature of the return air entering the unit.
RETURN FAN OUTPUT
This is the Binary output from the Unit Controller to the Return Fan control system.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
RETURN FAN PRESS CURRENT
This is the actual pressure in the mixed air chamber of the unit.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
RETURN FAN PRESSURE ACTIVE
SP
This is the current mixed air chamber pressure that the Unit Controller is trying to
maintain.
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT)
TABLE 93
-
PARAMETER DEFINITIONS (CONT'D)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...