208
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 91 - LON POINTS LIST (CONT'D)
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
BACnet
OBJECT
TYPE
AND IN-
STANCE
SNVT
POINTS LIST DESCRIPTION
nvoSEN_MSC_FLT
SENSOR / MISC
FAULT
BI-054
SNVT_switch
(95)
IDENTIFIES IF A SENSOR OR MISCELLANEOUS FAULT IS PRES
-
ENT (0 - NO FAULT;1 - FAULTED)
nvoSF_PROV_SW
SF PROVING
SWITCH
BI-055
SNVT_switch
(95)
THE STATUS OF THE SUPPLY FAN AIR PROVING CIRCUIT (RUN
- VERIFICATION CIRCUIT CLOSED / STO - STOP - VERIFICATION
CIRCUIT OPEN)
nviSTG_1_COOL
STG 1 COOLING
AV-031
SNVT_count_f
(51)
FOR A CONSTANT VOLUME UNIT THIS IS THE ACTIVE SAT SET
POINT FOR A FIRST STAGE COOLING DEMAND (F)
nviSTG_1_HEAT
STG 1 HEATING
AV-032
SNVT_count_f
(51)
FOR A CONSTANT VOLUME UNIT THIS IS THE ACTIVE SAT SET
POINT FOR A FIRST STAGE HEATING DEMAND (F)
nviSTG_2_COOL
STG 2 COOLING
AV-033
SNVT_count_f
(51)
FOR A CONSTANT VOLUME UNIT THIS IS THE ACTIVE SAT SET
POINT FOR A SECOND STAGE COOLING DEMAND (F)
nviSTG_2_HEAT
STG 2 HEATING
AV-034
SNVT_count_f
(51)
FOR A CONSTANT VOLUME UNIT THIS IS THE ACTIVE SAT SET
POINT FOR A SECOND STAGE HEATING DEMAND (F)
nvoSUP_AIR_TEMP
SUPPLY AIR TEMP
AI-046
SNVT_count_f
(51)
ACTUAL SUPPLY AIR TEMPERATURE (F)
nvoSUP_AIR_TRST
SUPPLY AIR TEMP
RST
A-0I47
SNVT_count_f
(51)
THIS IS EITHER A HARDWIRED OR COMMUNICATED 0 TO 5VDC
INPUT THAT ADJUST THE SUPPLY AIR SET POINT BETWEEN
THE SAT LOW AND SAT HIGH LIMIT (V)
SUP_FAN_VFD
SUPPLY FAN VFD
AI48
THE ACTUAL OUPUT TO THE SUPPLY FAN VFD (%)
nvoSUPPLY_FAN
SUPPLY FAN
BI-059
SNVT_switch
(95)
THE STATUS OF THE BINARY OUPUT FROM THE CONTROLLER
TO THE SUPPLY FAN CIRCUIT (ON / OFF)
nviSYSTEM_STOP
SYSTEM STOP
AV-035
SNVT_count
(8)
A 0- VALLUE ALLOWS ALL COMPRESSORS TO OPERATE;
1 - TURNS OFF COMPRESSOR SYSTEM 1; 2 - TURNS OFF COM
-
PRESSOR SYSTEM 2; 3 - TURNS OFF COMPRESSOR SYSTEM 3
nvoTEMP_1_SUCTION
TEMPERATURE 1
SUCTION
AI-049
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoTEMP_2_SUCTION
TEMPERATURE 2
SUCTION
AI-051
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoTEMP_3_SUCTION
TEMPERATURE 3
SUCTION
AI-053
SNVT_count_f
(51)
THIS FEATURE IS NOT AVAILABLE ON THIS UNIT.
nvoUND_FLR_DEWP
UNDER FLOOR
DEW POINT
AI-055
SNVT_count_f
(51)
THE CALACULATED DEW POINT OF THE AIR UNDER THE
FLOOR IN A FLEXSYS SYSTEM (%)
nviUND_HUMD_BAS
UNDER FLOOR
HUMIDITY BAS
AV-036
SNVT_switch
(95)
THIS ALLOWS THE BAS SYSTEM TO INPUT A UNDER FLOOR
HUMIDITY VALUE TO THE CONTROL ON A FLEXSYS SYSTEM
(%) "UNDER FLR HUMI BAS" MUST BE ENABLED USING THE
SERVICE KEY IN ORDER TO USE THIS FEATURE
nvoUND_FLR_HUMD
UNDER FLOOR
HUMIDITY
AI-056
SNVT_switch
(95)
HUMIDITY VALUE OF THE AIR UNDER THE FLOOR THE CON
-
TROL IS CONTROLLING TO IN A FLEXSYS SYSTEM (%)
nviUND_TEMP_BAS
UNDER FLOOR
TEMP BAS
AV-037
SNVT_count_f
(51)
THIS ALLOWS THE BAS SYSTEM TO INPUT A UNDER FLOOR
TEMPERATURE VALUE TO THE CONTROL ON A FLEXSYS SYS
-
TEM (F). "UNDER FLR TEMP BAS" MUST BE ENABLED USING
THE SERVICE KEY IN ORDER TO USE THIS FEATURE
nvoUND_FLR_TEMP
UNDER FLOOR
TEMP
AI-057
SNVT_count_f
(51)
TEMPERATURE OF THE AIR UNDER THE FLOOR THE CONTROL
IS CONTROLLING TO IN A FLEXSYS SYSTEM (F)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...