24
JOHNSON CONTROLS
5276178-JIM-C-0118
Installation
TALBE 3 - STANDARD GAS HEATING CAPACITIES
present from the following sources:
• Commercial buildings
• Indoor pools
• Laundry rooms
• Hobby or craft rooms
• Chemical storage areas
The following substances should be
avoided to maintain outdoor combus
-
tion air quality:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool cleaners
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
•
Cleaning solvents (such as perchloroethylene)
•
Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
GAS HEAT
OPTION
AVAILABLE
ON MODELS
INPUT CAPACITY (MBH)
1
OUTPUT
CAPACITY
(MBH)
2
GAS RATE, CU. FT./HR.
3
1ST STAGE
TOTAL
1ST STAGE
TOTAL
N3
S2/S3/S4
267
267
213
247
247
N5
S2/S3/S4
267
533
426
247
495
N8
S4 ONLY
267
4
800
638
247
742
1. Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
2. Blower motor heat not included.
3. Based on a heat content of 1075 BTU/Ft.
3
GAS RATE = Input MBH
3
(
1.075MBH
)/Ft
4. Unit Control Board with 3 heating outputs only. For all other Unit Control Boards the 1st Stage is 533 MBH.
TABLE 4 - TEMPERATURE RISE
TON
MODULES
1
2
3
25
5-35
25-55
-
30
5-35
20-50
-
40
5-30
10-45
25-55
TABLE 5 - MINIMUM HEATING CFM
TON
MODULES
1
2
3
25
5,644
7,183
-
30
5,644
7,901
-
40
6,584
8,779
13,169
(GAS HEATING OPERATION)
Excessive exposure to contaminated
combustion air will result in safety
and performance related problems. To
maintain combustion air quality, the
recommended source of combustion
air is the outdoor air supply.
The outdoor air supplied for combus
-
tion should be free from contaminants
due to chemical exposure that may be
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...