Start-up
COMPRESSORS
Each compressor is inherently protected from over
current and over temperature. High and low pressure
switches are installed on the discharge and suction lines
respectively for high and low pressure protection.
MOTORS
Indoor Blower Motors
All indoor blower motors are non-inherently protected
three phase motors. Overcurrent protection is provided
by a manual reset starter/overload relay and short circuit
protection is provided by fuses.
Power Exhaust Fan Motors
All motors are non-inherently protected three phase
TABLE 52 - STEAM COIL (1 ROW, 25 & 30 TON)
CFM
CAPACITY (MBH) AT STEAM PRESSURE (PSI)
2
6
10
15
6000
194.1
207.9
219.8
232.6
8000
221.1
236.9
250.4
265.0
10000
243.2
260.5
275.4
291.4
12000
261.9
280.6
296.6
313.9
15000
285.6
306.0
323.5
342.4
1. Based on 60°F entering air temperature, 2.00” Maximum air pressure drop across the coil.
TABLE 54 - STATIC RESISTANCE STEAM COIL (25 & 30 TON)
CFM
6000
8000
10000
12000
15000
AIR PRESSURE DROP
0.11
0.18
0.26
0.36
0.54
TABLE 53 - STEAM COIL (1 ROW, 40 TON)
CFM
CAPACITY (MBH) AT STEAM PRESSURE (PSI)
2
6
10
15
8000
221.1
236.9
250.4
265.0
11000
252.9
271.0
286.4
303.1
14000
278.2
298.0
315.0
333.4
17000
299.4
320.7
339.0
358.8
20000
317.6
340.2
359.6
380.6
1. Based on 60°F entering air temperature, 2.00” maxi air pressure drop across the coil.
motors. Overcurrent protection is provided by a manual
reset starter/overload relay and short circuit protection
is provided by fuses.
Condenser Fan Motors
All condenser fan motors are inherently protected three
phase motors. Short circuit protection is provided by
fuses.
Draft Motor (Gas Furnace)
All draft motors are line voltage, inherently protected,
single phase PSC motors. Short circuit protection is
provided by fuses.
HOT WATER AND STEAM COILS
See Tables 39 through 51 for information on Hot Water
and Steam Coils.
TABLE 55 - STATIC RESISTANCE STEAM COIL (40 TON)
CFM
8000
11000
14000
17000
20000
AIR PRESSURE DROP
0.18
0.31
0.48
0.67
0.88
1
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...