194
JOHNSON CONTROLS
5276178-JIM-C-0118
User Interface Control Center
TABLE 90
-
BACNET MS/TP, MODBUS, BACNET IP
(See notes at end of table)
BACnet NAME
USER
INTERFACE
NAME
READ/
WRITE
BACnet
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
ACT _DSP_SP
DUCT STATIC SET
POINT
R
AI01
514
A DERIVED VALUE THE DUCT STATIC IS
CONTROLLED TO (“WC)
ACT_MIN_FLOW
ACTIVE MINIMUM
AIR FLOW
R
AI02
515
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
ACT_MIN_POS
ACTIVE MINIMUM
POSITION
R
AI03
516
A DERIVED VALUE THE DAMPER IS CONTROLLED
TO FOR MINIMUM VENTILATION AIR (%)
ACT_SAT_SP
SUPPLY AIR SETP
R
AI04
517
A DERIVED VALUE THE SUPPLY AIR TEMPERATURE
IS CONTROLLED TO (F)
ACT_SLAB_CTL
ACTIVE SLAB
CONTROL
R/W
AV77
1102
ALLOWS THE ACTIVE SLAB CONTROL FEATURE TO
BE TURNED ON AND OFF ON FLEXSYS UNITS (0 =
OFF / 1 = ON)
AMORN_WA_ACT
ADAPT MORN
WARM UP ACTIVE
R
BI01
1282
IDENTIFIES WHEN ADPACTIVE MORING MORN UP
IS ACTIVE (OFF / ON)
BLD_STAT_PRS
BUILDING STATIC
PRES
R
AI05
518
ACTUAL BUILDING PRESSURE INPUT (“WC)
BUILD_PRES_SP
BUILDING
PRESSURE SP
R/W
AV01
1026
THE BUILDING PRESSURE SET POINT (“WC)
BYPASS_DAMPER
BYPASS DAMPER
R
AI06
519
ACTUAL BYPASS DAMPER POSITION (%)
C02_2_INSIDE
CO
2
1 (INSIDE)
R
AI08
521
ACTUAL INDOOR CO
2
VALUE (PPM)
C02_INSIDE
CO
2
lvl inside value
bas
R/W
AV43
1168
A BAS ENTERED VALUE FOR THE INSIDE CO
2
LEVEL. “CO
2
LVL INSIDE BAS” MUST BE ENABLED
USING THE SERVICE KEY IN ORDER TO USE THIS
FEATURE.
CO
2
_1_OUT
CO
2
1 (OUTSIDE)
R
AI07
520
ACTUAL OUTDOOR CO
2
VALUE (PPM)
CO
2
_OFFSET
CO
2
OFFSET
R/W
AV02
1027
THE DIFFERENCE BETWEEN THE INDOOR AND
OUTSIDE CO
2
MUST EXCEED THIS VALUE TO
INITIATE DEMAND VENTILATION (PPM)
COL_HEAT_FLT
COOLING/HEATING
FAULT
R
BI02
1283
GIVES THE FAULT STATUS OF THE COOLING AND
HEATING SYSTEM (0 - NO FAULT; 1 - FAULTED)
COMFORT_VENT
COMFORT
VENTILATION
R/W
AV(BV)78
1103
GIVES THE STATUS OF THE COMFORT VENT
OPTION AND ALLOWS IT TO BE TURNED ON AND
OFF (0 = OFF; 1 = ON)
COMP_1A
COMPRESSOR 1A
R
BI03
1284
STATUS OF COMPRESSOR 1 (0 = OFF, 1 = ON)
COMP_1A_OPER
COMPRESSOR 1A
OPER HRS
R
AI09
522
THE NUMBER OF HOURS COMPRESSOR 1 HAS
BEEN IN OPERATION (HOUR)
COMP_1B
COMPRESSOR 1B
R
BI04
1285
STATUS OF COMPRESSOR 2 (0 = OFF, 1 = ON)
COMP_1B_OPER
COMPRESSOR 1B
OPER HRS
R
AI10
523
THE NUMBER OF HOURS COMPRESSOR 2 HAS
BEEN IN OPERATION (HOUR)
COMP_2A
COMPRESSOR 2A
R
BI05
1286
STATUS OF COMPRESSOR 3 (0 = OFF, 1 = ON)
COMP_2A_OPER
COMPRESSOR 2A
OPER HRS
R
AI11
524
THE NUMBER OF HOURS COMPRESSOR 3 HAS
BEEN IN OPERATION (HOUR)
COMP_2B
COMPRESSOR 2B
R
BI06
1287
STATUS OF COMPRESSOR 4 (0 = OFF, 1 = ON)
COMP_2B_OPER
COMPRESSOR 2B
OPER HRS
R
AI12
525
THE NUMBER OF HOURS COMPRESSOR 4 HAS
BEEN IN OPERATION (HOUR)
COMP_3A
COMPRESSOR 3A
R
BI07
1288
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
COMP_3A_OPER
COMPRESSOR 3A
OPER HRS
R
AI13
526
THIS FEATURE IS NOT AVAILABLE ON
THIS UNIT.
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...