62
JOHNSON CONTROLS
5276178-JIM-C-0118
Installation
Volt
Compressors
(each)
OD Fan
Motors
(each)
Heat Option
Conv
Outlet
Supply
Blower
Motor
Pwr
Exh
Motor
W/O Pwrd Conv
Outlet
With Pwrd Conv
Outlet
MCA
1
Max
Fuse
2
/
Breaker
3
Size
MCA
1
Max
Fuse
2
/
Breaker
3
Size
QTY RLA
LRA
MCC
FLA
Model kW
Stages Amps
FLA HP FLA HP FLA
Amps
Amps
Amps
Amps
575-3-60
4
7.7
54
12
1.7
None/
Gas
-
-
-
4.2
7.5
9
-
-
49
50
53
60
5
6.1
55
60
59
60
7.5
9
58
60
62
70
10
11
60
70
65
70
10
11
-
-
51
60
56
60
5
6.1
57
60
62
70
7.5
9
60
70
65
70
10
11
62
70
67
70
15
17
-
-
59
70
63
80
5
6.1
65
80
69
80
7.5
9
68
80
72
80
10
11
70
80
74
90
20
22
-
-
65
80
69
90
5
6.1
71
90
75
90
7.5
9
74
90
78
100
10
11
76
90
80
100
575-3-60
4
7.7
54
12
1.7
E4
40
1
40
4.2
7.5
9
-
-
61
70
65
70
5
6.1
67
70
72
80
7.5
9
70
70
74
80
10
11
73
80
77
80
10
11
-
-
64
70
68
70
5
6.1
70
80
74
80
7.5
9
73
80
77
80
10
11
75
80
79
90
15
17
-
-
71
80
75
90
5
6.1
77
90
82
90
7.5
9
80
90
84
100
10
11
82
90
86
100
20
22
-
-
78
100
82
100
5
6.1
84
100
88
110
7.5
9
87
100
91
110
10
11
89
110
93
110
575-3-60
4
7.7
54
12
1.7
E8
80
2
80
4.2
7.5
9
-
-
91
100
95
100
5
6.1
97
100
102
110
7.5
9
100
100
104
110
10
11
103
110
107
110
10
11
-
-
94
100
98
100
5
6.1
100
110
104
110
7.5
9
103
110
107
110
10
11
105
110
109
110
15
17
-
-
101
110
105
110
5
6.1
107
110
112
125
7.5
9
110
125
114
125
10
11
112
125
116
125
20
22
-
-
108
125
112
125
5
6.1
114
125
118
125
7.5
9
117
125
121
125
10
11
119
125
123
125
575-3-60
4
7.7
54
12
1.7
E1
108
2
108
4.2
7.5
9
-
-
119
150
123
150
5
6.1
125
150
130
150
7.5
9
128
150
132
150
10
11
131
150
135
150
10
11
-
-
122
150
126
150
5
6.1
128
150
132
150
7.5
9
131
150
135
150
10
11
133
150
137
150
15
17
-
-
129
150
133
150
5
6.1
135
150
140
150
7.5
9
138
150
142
150
10
11
140
150
144
150
20
22
-
-
136
150
140
150
5
6.1
142
150
146
150
7.5
9
145
150
149
150
10
11
147
150
151
175
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
TABLE 26 ELECTRICAL DATA 25 TON 575 VOLT WITHOUT ERV
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...