DISPLAY TEXT
PASS
WORD
LEVEL
RANGE
DEFAULT
SETTING
LOCATION
SHOW WHEN UNIT TYPE IS
DEW POINT RESET
1
USER ENABLED USER
DISABLED
USER DISABLED
PROGRAM/
COOLING
UNIT TYPE EQUALS FLEXSYS
UNDER FLR TEMP OVRD
1
ACTIVE - INACTIVE
DERIVED
UNIT TYPE EQUALS FLEXSYS
ACTIVE SLAB CONTROL
1
USER ENABLED USER
DISABLED
USER DISABLED
PROGRAM/
COOLING
UNIT TYPE EQUALS FLEXSYS
1ST STAGE COOLING
SETPOINT
1
55.0º F TO 60.0º F
60.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS CONSTANT
VOLUME
2ND STAGE COOLING
SETPOINT
1
50.0º F TO 60.0º F
55.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS CONSTANT
VOLUME
SAT LOW SETPOINT
1
50.0º F - 60.0º F
55.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM
SAT HIGH SETPOINT
1
55.0º F - 65.0º F
65.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM
OAT SETPOINT FOR
LOW SAT
1
OAT SETPOINT FOR
HIGH SAT TO 90º F
80.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM AND SAT RESET METHOD
EQUALS OUTSIDE TEMP
HIGH SAT
1
60.0º F TO OAT
SETPOINT FOR LOW
SAT
70.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM AND SAT RESET METHOD
EQUALS OUTSIDE TEMP
RAT SETPOINT FOR
LOW SAT
1
RAT SETPOINT FOR
HIGH RAT +5.0º F TO
90.0º F
90.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM AND SAT RESET METHOD
EQUALS RETURN TEMP
HIGH SAT
1
RAT COOLING
SETPOINT TO RAT
SETPOINT FOR LOW
SAT -5º F
80.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM AND SAT RESET METHOD
EQUALS RETURN TEMP
FAN SPEED SETP FOR
LOW SAT
1
FAN SPEED SETP FOR
HIGH SAT TO 100%
90%
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM AND SAT RESET METHOD
EQUALS SUPPLY FAN SPEED
HIGH SAT
1
50% TO FAN SPEED
SETP FOR LOW SAT
70%
SETPOINTS/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM AND SAT RESET METHOD
EQUALS SUPPLY FAN SPEED
EVAP LEAVING AIR TEMP
HIGH
1
50.0º F - 60.0º F
60.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS FLEXSYS
EVAP LEAVING AIR TEMP
LOW
1
50.0º F - 60.0º F
50.0º F
SETPOINTS/
COOLING
UNIT TYPE EQUALS FLEXSYS
RESET ENTHALPY SP
2
25 TO 35 BTU
30 BTU/#
SETPOINTS/
COOLING
UNIT TYPE EQUALS FLEXSYS
SUP AIR TEMPERING
2
USER ENABLED USER
DISABLED
USER DISABLE
PROGRAM/
COOLING
UNIT TYPE EQUALS VARIABLE AIR
VOLUM OR FLEXSYS
MECH CLG LOCKOUT
TEMP
1
0.0º F - 65.0º F
50.0º F
SETPOINTS/
COOLING
PRESS TRANS PKG AND LOW AMBIENT
PKG OTHER THAN NONE
MECH CLG LOCKOUT
TMP MINIMUM
2
-10.0º F - 0.0º F
0.0º F
SETPOINTS/
COOLING
PRESS TRANS PKG AND LOW AMBIENT
PKG OTHER THAN NONE
TABLE 81 - COOLING (CONT'D)
Summary of Contents for 40 25 TON
Page 22: ...22 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 35: ...35 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 10 PARTIAL ROOF CURB MODEL 1RC0455P LD14177 ...
Page 41: ...41 2 JOHNSON CONTROLS 5276178 JIM C 0118 FIGURE 18 40 TON FORWARD CURVE EXAMPLE ...
Page 159: ...159 JOHNSON CONTROLS 5276178 JIM C 0118 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 244: ...244 JOHNSON CONTROLS 5276178 JIM C 0118 Service NOTES ...