background image

DAIKIN ROOM AIR CONDITIONER

INSTALLATION MANUAL

R410A Split Series

English

Français

Español

MODELS

FTXS09LVJU
FTXS12LVJU
CTXS07LVJU

00_CV_3P297301-1.indd   1

10/18/2011   6:25:17 PM

Summary of Contents for SUPER MULTI NX FTXS09LVJU

Page 1: ...DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series English Fran ais Espa ol MODELS FTXS09LVJU FTXS12LVJU CTXS07LVJU 00_CV_3P297301 1 indd 1 10 18 2011 6 25 17 PM...

Page 2: ...or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to s...

Page 3: ...P bands for a means of transportation It is dangerous Electrical work must be performed in accordance with the NEC CEC by authorized personnel only Accessories Indoor unit A L Mounting plate 1 Remote...

Page 4: ...r lter Tab Wrap the thermal insulation pipe with the nishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the i...

Page 5: ...l method 1 Remove front panel to remove the air filter 2 Remove 2 screws from the front grille 3 In front of the mark of the front grille there are 3 upper hooks Lightly pull the front grille toward y...

Page 6: ...to the S21 connector and pull the harness out through the notched part in the figure 3 Replace the electrical wiring cover as it was and pull the harness around as shown in the figure HA connector S2...

Page 7: ...at the chips do not enter the pipe 3 Put the flare nut on the pipe 4 Flare the pipe 5 Check that the flaring is properly made Set exactly at the position shown below A Flaring Die A 0 0 020 inch 0 0 5...

Page 8: ...e pipe against dust and moisture 2 All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no are cap is available cover the are mouth with tape to keep dirt or water out...

Page 9: ...ce cut out from the unit for piping 2 5 16 59 5 2 3 8 60 5 7 8 149 10 15 16 278 5 1 15 16 50 31 1 2 800 1 7 16 36 Removed pipe port cover Mounting plate Place a leveler on raised tab 2 9 16 65 A Gas p...

Page 10: ...plug No gap Do not apply lubricating oil refrigeration oil when inserting Application of causes deterioration and drain leakage of the plug Insert a hexagonal wrench 3 16 4mm 4 Shape the refrigerant p...

Page 11: ...wires are securely fixed to the terminal block 7 In case of connecting to an adapter system run the remote controller cable and attach the S21 Refer to P5 when connecting to an HA system 8 Shape the w...

Page 12: ...ion of the extension hose Indoor unit drain hose 5 8 16mm Extension drain hose Heat insulation tube eld supply 4 When connecting a rigid polyvinyl chloride pipe nominal diameter 1 2 inch 13mm directly...

Page 13: ...wer to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again Trial operation from remote controller 1 Press ON OFF button to turn on the syst...

Page 14: ...Two dimensional bar code is a code for manufacturing 3P297301 1 M11B119 1111 HT 00_CV_3P297301 1 indd 2 10 18 2011 6 25 17 PM...

Reviews: