2

English

Safety Precautions

 WARNING

• During pump-down, stop the compressor before removing the refrigerant piping.

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, 
causing abnormally high pressure which could lead to equipment damage or and personal injury.

• During installation, attach the refrigerant piping securely before running the compressor.

If the refrigerant pipes are not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, 
causing abnormally high pressure which could lead to equipment damage and personal injury.

• Be sure to install a ground fault circuit interrupter breaker.

Failure to install a ground fault circuit interrupter breaker may result in electrically shocks, or fire personal injury.

 CAUTION

• Do not install the air conditioner where gas leakage would be exposed to open flames.

If the gas leaks and builds up around the unit, it may catch fire.

• Establish drain piping according to the instructions of this manual. 

Inadequate piping may cause water damage.

• Tighten the flare nut according to the specified torque. A torque wrench should be used.

If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.

• Do not touch the heat exchanger fins.

Improper handling may result in injury.

• Be very careful about product transportation.

Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.

• Electrical work must be performed in accordance with the NEC/CEC by authorized personnel only.

Accessories

Indoor unit

A  – 

L

,

 

Mounting plate

1

 

Remote controller holder

1

 

Tube

1

 

Mounting plate fixing screw 
3/16” × 1” (M4 × 25mm)

5

 

Fixing screw for remote controller 
holder 1/8” × 13/16” (M3 × 20mm)

2

 

Operation manual

1

 

Titanium apatite photocatalytic 
air-purifying filter

2

 

Dry battery AAA. LR03  
(alkaline)

2

 

Installation manual

1

 

Wireless remote controller

1

 

Indoor unit fixing screw  
 3/16” × 1/2” (M4 × 12mm)

2

Choosing an Installation Site

• Before choosing the installation site, obtain user approval.

1. 

Indoor unit

• The indoor unit should be sited in a place where: 

1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air inlet and air outlet have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool (warm) air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the 

remote controller range,

8) the unit is at least 3.5ft (1m) away from any television or radio set (unit may cause interference with the picture or sound),
9) install at the recommended height 6ft (1.8m),

10) no laundry equipment is located in the space.

2. 

Wireless remote controller

1) Turn on all the fluorescent lamps in the room, if any, and find the site where remote control signals are properly 

received by the indoor unit (within 23ft/7m).

A

E

J

B

F

K

C

G

L

D

H

01_EN_3P297301-1.indd   2

10/20/2011   2:38:22 PM

Summary of Contents for SUPER MULTI NX FTXS09LVJU

Page 1: ...DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series English Fran ais Espa ol MODELS FTXS09LVJU FTXS12LVJU CTXS07LVJU 00_CV_3P297301 1 indd 1 10 18 2011 6 25 17 PM...

Page 2: ...or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to s...

Page 3: ...P bands for a means of transportation It is dangerous Electrical work must be performed in accordance with the NEC CEC by authorized personnel only Accessories Indoor unit A L Mounting plate 1 Remote...

Page 4: ...r lter Tab Wrap the thermal insulation pipe with the nishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the i...

Page 5: ...l method 1 Remove front panel to remove the air filter 2 Remove 2 screws from the front grille 3 In front of the mark of the front grille there are 3 upper hooks Lightly pull the front grille toward y...

Page 6: ...to the S21 connector and pull the harness out through the notched part in the figure 3 Replace the electrical wiring cover as it was and pull the harness around as shown in the figure HA connector S2...

Page 7: ...at the chips do not enter the pipe 3 Put the flare nut on the pipe 4 Flare the pipe 5 Check that the flaring is properly made Set exactly at the position shown below A Flaring Die A 0 0 020 inch 0 0 5...

Page 8: ...e pipe against dust and moisture 2 All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no are cap is available cover the are mouth with tape to keep dirt or water out...

Page 9: ...ce cut out from the unit for piping 2 5 16 59 5 2 3 8 60 5 7 8 149 10 15 16 278 5 1 15 16 50 31 1 2 800 1 7 16 36 Removed pipe port cover Mounting plate Place a leveler on raised tab 2 9 16 65 A Gas p...

Page 10: ...plug No gap Do not apply lubricating oil refrigeration oil when inserting Application of causes deterioration and drain leakage of the plug Insert a hexagonal wrench 3 16 4mm 4 Shape the refrigerant p...

Page 11: ...wires are securely fixed to the terminal block 7 In case of connecting to an adapter system run the remote controller cable and attach the S21 Refer to P5 when connecting to an HA system 8 Shape the w...

Page 12: ...ion of the extension hose Indoor unit drain hose 5 8 16mm Extension drain hose Heat insulation tube eld supply 4 When connecting a rigid polyvinyl chloride pipe nominal diameter 1 2 inch 13mm directly...

Page 13: ...wer to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again Trial operation from remote controller 1 Press ON OFF button to turn on the syst...