Trial Operation and Testing

1. 

Trial operation and testing

1-1  Measure the supply voltage and make sure that it falls in the specified range.
1-2  Trial operation should be carried out in either cooling or heating mode.

• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable 

temperature.
1) Trial operation may be disabled in either mode depending on the room temperature.

Use the remote controller for trial operation as described below.

2) After trial operation is complete, set the temperature to a normal level (78°F to 82°F (26°C to 28°C) in cooling mode, 

68°F to 75°F (20°C to 24°C) in heating mode).

3) For protection, the system disables restart operation for 3 minutes after it is turned off.

1-3  Carry out the test operation in accordance with the operation manual to ensure that all functions and parts, 

such as fin movement, are working properly.

• The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for some 

time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.

• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation 

mode when the circuit breaker is opened again.

Trial operation from remote controller

1) Press “ON/OFF” button to turn on the system.
2) Press “TEMP” button (2 locations) and “MODE” button at the same time.
3) Press “MODE” button twice.

(“ 

T

 ” will appear on the display to indicate that trial operation mode is selected.)

4) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press “ON/

OFF” button.

2. 

Test items

Test items

Symptom 

(diagnostic display on RC)

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating 
function

Refrigerant gas and liquid pipes and indoor drain hose extension are 
thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly grounded.

Electrical leakage

The specified wires are used for inter-unit wiring.

Inoperative or burn damage

Indoor or outdoor unit’s air inlet or air outlet has clear path of air. 
Stop valves are opened.

Incomplete cooling/heating 
function

Indoor unit properly receives remote control commands.

Inoperative

The heat pump or cooling only mode is selectable with the DIP switch of 
the remote controller.

Remote controller malfunction

-

ing

01_EN_3P297301-1.indd   12

10/20/2011   2:38:30 PM

Summary of Contents for SUPER MULTI NX FTXS09LVJU

Page 1: ...DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series English Fran ais Espa ol MODELS FTXS09LVJU FTXS12LVJU CTXS07LVJU 00_CV_3P297301 1 indd 1 10 18 2011 6 25 17 PM...

Page 2: ...or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to s...

Page 3: ...P bands for a means of transportation It is dangerous Electrical work must be performed in accordance with the NEC CEC by authorized personnel only Accessories Indoor unit A L Mounting plate 1 Remote...

Page 4: ...r lter Tab Wrap the thermal insulation pipe with the nishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the i...

Page 5: ...l method 1 Remove front panel to remove the air filter 2 Remove 2 screws from the front grille 3 In front of the mark of the front grille there are 3 upper hooks Lightly pull the front grille toward y...

Page 6: ...to the S21 connector and pull the harness out through the notched part in the figure 3 Replace the electrical wiring cover as it was and pull the harness around as shown in the figure HA connector S2...

Page 7: ...at the chips do not enter the pipe 3 Put the flare nut on the pipe 4 Flare the pipe 5 Check that the flaring is properly made Set exactly at the position shown below A Flaring Die A 0 0 020 inch 0 0 5...

Page 8: ...e pipe against dust and moisture 2 All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no are cap is available cover the are mouth with tape to keep dirt or water out...

Page 9: ...ce cut out from the unit for piping 2 5 16 59 5 2 3 8 60 5 7 8 149 10 15 16 278 5 1 15 16 50 31 1 2 800 1 7 16 36 Removed pipe port cover Mounting plate Place a leveler on raised tab 2 9 16 65 A Gas p...

Page 10: ...plug No gap Do not apply lubricating oil refrigeration oil when inserting Application of causes deterioration and drain leakage of the plug Insert a hexagonal wrench 3 16 4mm 4 Shape the refrigerant p...

Page 11: ...wires are securely fixed to the terminal block 7 In case of connecting to an adapter system run the remote controller cable and attach the S21 Refer to P5 when connecting to an HA system 8 Shape the w...

Page 12: ...ion of the extension hose Indoor unit drain hose 5 8 16mm Extension drain hose Heat insulation tube eld supply 4 When connecting a rigid polyvinyl chloride pipe nominal diameter 1 2 inch 13mm directly...

Page 13: ...wer to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again Trial operation from remote controller 1 Press ON OFF button to turn on the syst...

Page 14: ...Two dimensional bar code is a code for manufacturing 3P297301 1 M11B119 1111 HT 00_CV_3P297301 1 indd 2 10 18 2011 6 25 17 PM...

Reviews: