8
■
English
Indoor Unit Installation
1.
Installing the mounting plate
• The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the boring
points on the wall.
2) Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
unit: inch (mm)
Liquid pipe end
Drain hose position
Through the wall hole
ϕ
2-9/16 (
ϕ
65mm)
* The removed pipe port cover can be
kept in the mounting plate pocket.
(Bolt size: 3/8(M10))
Recommended mounting plate
retention spots. (5 spots in all)
(Bolt size: 3/8(M10))
1-3/4 (44.5)
1-13/16 45.5
11-5/8 (295)
4-1/2 (115)
2-1/4 (56.5)
5-13/16 (147.5)
17-11/16 (450)
4-1/16 (103)
15-3/4 (400)
7-7/8 (200)
1-3/4 (44.5)
2-3/8 (60.5)
1-13/16 (45.5)
6-15/16 (175.5)
Keep here the piece cut out
from the unit for piping.
2-5/16
(59.5)
2-3/8
(60)
5-7/8 (149)
10-15/16 (278.5)
1-15/16
(50)
31-1/2 (800)
1-7/16 (36)
Removed pipe port
cover
Mounting plate
Place a leveler on raised tab.
ϕ
2-9/16
(
ϕ
65)
A
Gas pipe end
Use tape measure as
shown.
Position the end of a
tape measure at .
ϕ
2-9/16
(
ϕ
65)
2.
Boring a wall hole and installing wall embedded pipe
• For walls containing metal frame or metal board, be sure to use a wall
embedded pipe and wall cover in the feed-through hole to prevent possible
heat, electrical shock, or fire.
• Be sure to caulk the gaps around the pipes with caulking material to prevent
water leakage.
1) Bore a feed-through hole of 2-9/16 inch (65mm) in the wall so it has a
down slope toward the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk pipe
hole gap with putty.
Inside
Outside
Caulking
Wall embedded pipe
(field supply)
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
ϕ
2-9/16”
(
ϕ
65mm)