P06
Motor (No-load current)
P07
Motor (%R1)
P08
Motor (%X)
These function codes specify no-load current, %R1, and %X. Obtain the appropriate values from the
test report of the motor or by calling the manufacturer of the motor. By performing auto tuning, these
parameters are automatically set as well.
■
No-load current (P06)
Enter the value obtained from the motor manufacturer.
- Data setting range: 0.00 to 500.0 (A)
■
%R1 (P07)
Enter the value calculated by the following formula.
(%)
100
×
)
I
×
3
(
/
V
R1
Cable
R1
%R1
+
=
where,
R1: Primary resistance of the motor (
Ω
)
Cable R1: Resistance of the output cable (
Ω
)
V: Rated voltage of the motor (V)
I:
Rated current of the motor (A)
- Data setting range: 0.00 to 50.00 (%)
■
%X (P08)
Enter the value calculated by the following formula.
(%)
100
×
)
I
×
3
(
/
V
X
Cable
XM)
(X2
/
XM
×
X2
X1
%X
+
+
+
=
X1: Primary leakage reactance of the motor (
Ω
)
X2: Secondary leakage reactance of the motor (converted to primary) (
Ω
)
XM: Exciting reactance of the motor (
Ω
)
Cable X: Reactance of the output cable (
Ω
)
V: Rated voltage of the motor (V)
I: Rated current of the motor (A)
- Data setting range: 0.00 to 50.00 (%)
For reactance, choose the value at the base speed (F04).
2-86