C codes (Control functions)
2.3.3
C01
Battery Operation (Limit level)
C01 and C02 specify the limitation level and detection time in battery operation. The limitation
method is depending on the control mode.
- Data setting range(C01): 0 to 100 (%) (The meaning of 100% is 10kW)
OFF (no operation)
- Data setting range(C02): 0.0 to 30.0 (s)
■
Input power limitation
When the input power has exceeded the level specified C01 and this condition continues longer than
the period specified by C02 (Limit time) the inverter stops automatically and
IPL
comes ON. It turns
OFF when FWD or REV command turns OFF.
BATRY
73X
Battery power
supply
Run command
Manual Speed
(Middle)
Output frequency
C03
The inverter stops
ON
ON
ON
ON
ON
E17
0
Input power
C01
0
C02
IPL
ON
The inverter stops
automatically
BRKS
ON
C03
Battery Operation Speed
C03 specifies the battery operation speed. When the manual speed (middle) is selected in battery
operation, the inverter operates with this speed.
- Data setting range: 0.00 to 6000 (r/min)
Data setting range changes depending on the number of poles of motor etc. For details, refer to
section 2.2.
■
Battery operation
The battery operation allows an inverter to run the elevator with a battery (or UPS) in undervoltage
condition. The purpose of this funtion is to rescues the passengers from the cabin stopped halfway
due to a power failure. Using battery operation, the inverter moves the cabin to the nearest floor.
C02
Battery Operation (Limit time)
2-76