2.3 Overview of Function Code
C
hap.
2
FUN
CT
IO
N
C
O
D
E
S
Example combination of
SS1
,
SS2, SS4
and
SS8
states to enable reference speeds (pre-ramp)
To select zero speed by turning on
SS1
, for example, configure a multistep speed command by
setting
SS1, SS2, SS4 and SS8
and L11 to L18 as listed below.
SS8
SS4
SS2
SS1
L11 to L18
Reference speed (pre-ramp)
selected
OFF
OFF
OFF
ON
L11 = 00000001
b
Zero speed defined by C04
OFF
OFF
OFF
OFF
L12 = 00000000
b
Manual speed (middle) defined by C05
OFF
OFF
ON
OFF
L13 = 00000010
b
Maintenance speed defined by C06
OFF
OFF
ON
ON
L14 = 00000011
b
Creep speed defined by C07
OFF
ON
OFF
OFF
L15 = 00000100
b
Manual speed (low) defined by C08
OFF
ON
OFF
ON
L16 = 00000101
b
Low speed defined by C09
OFF
ON
ON
OFF
L17 = 00000110
b
Middle speed defined by C10
OFF
ON
ON
ON
L18 = 00000111
b
High speed 1 defined by C11
ON
OFF
OFF
ON
—
High speed 2 defined by C12
ON
OFF
OFF
OFF
—
High speed 3 defined by C13
ON
OFF
ON
OFF
—
High speed 4 defined by C14
ON
OFF
ON
ON
—
High speed 5 defined by C15
ON
ON
OFF
OFF
—
High speed 6 defined by C16
ON
ON
OFF
ON
—
High speed 7 defined by C17
ON
ON
ON
OFF
—
High speed 8 defined by C18
ON
ON
ON
ON
—
High speed 9 defined by C19
Do not double assign the same data to L11 (Zero Speed) to L18 (High Speed 1). Eight
values are available, ranging from "00000000" to "00000111." Double assignment results
in a trip with alarm
Er6
the moment a run command is entered.
It is recommended that, speeds from zero to high speed 1 are used for same purpose as
the function code name. To use any of them for different purposes, confirm the setting
ranges of its acceleration/deceleration time and S-curve acceleration/deceleration time.
2-27