Run command
(FWD, REV)
SCCF
BRKE
BRKS
Short-circuit contact
IGBT’s gate
SCC
ALM
ON (OPEN)
ON
OFF
OFF
ON
ON
Inverter trips Er6 (SUB= 8)
L84
OPEN
CLOSED
OFF
Figure 8. Brake opened by external means.
Case 4:
STBY
input function is ON
Figure 9 shows the case when stand-by mode function (
STBY
) is enabled. In this case energy will be
saved by not keeping energized motor short circuit conactor.
Run command
(FWD, REV)
SCCF
STBY
(pending)
BRKS
Short-circuit contact
IGBT’s gate
SCC
ALM
ON
ON
OFF
OFF
ON
OPEN
CLOSED
OFF
ON
OPEN
ON
OFF
Figure 9.
STBY
function enabled.
L122
Deliverance Operation (Input power detection level)
L123
Deliverance Operation (Direction Calculation Setup)
L124
Deliverance Operation (Direction Calculation Delay Timer)
This function calculates the best direction to perform the movement (FWD or REV), when a vertical load
with a counterweight has to be moved and the requirements about the input power are very restrictive (i.e.,
supplying the inverter by means of a UPS system or batteries).
■
Input power detection level (L122)
On this parameter input power detection level is set. This level is used to decide to which direction run the
motor.
- Data setting range: 1 to 200 %
2-192
Summary of Contents for Frenic lift
Page 1: ...LM2A series Reference Manual INR SI47 1909a E...
Page 7: ......
Page 13: ......
Page 51: ...2 38...
Page 221: ......
Page 252: ......
Page 254: ...URL http www fujielectric com...