H codes (High performance functions)
2.3.5
H03
Data Initialization
Initialize all function code data to the factory defaults.
To change the H03 data, it is necessary to press the
+
/
keys (simultaneous keying).
H03 data
Function
0
Disable initialization (Settings manually made by the user will be retained.)
1
Initialize all function code data to the factory defaults (Vector control for asynchronous
motors)
2
System-specific initialization (Vector control for synchronous motors)
3
System-specific initialization (Open loop control for asynchronous motors)
11
Limited initialization (all except communications function codes)
12
Limited initialization (initialization of customizable logic function U/U1 codes)
Upon completion of the initialization, the H03 data reverts to "0" (factory default).
Initialize all function code data to factory defaults
(H03 = 1)
Initialize all function code data to the factory defaults. It is suited for vector control for asynchronous
motors.
Initialize function code data except communication function codes
(H03 = 11)
The function codes other than the communication function codes (y codes) are initialized.
Communication can be continued after initialization.
Initialize customizable logic U/U1 code data
(H03 = 12)
Initializes the customizable logic (U/U1 code) data. Any other function code data are not initialized.
2-88