Cancel customizable logic “CLC” (function codes E01 to E08 Data = 80)
Customizable logic operations can temporarily be disabled so that the inverter can be operated
without the customizable logic’s logical circuit and timer operation, for example during maintenance.
“CLC”
Function
OFF
Customizable logic enabled (according to U00 setting)
ON
Customizable logic disabled
If you turn ON the customizable logic cancellation signal “CLC”, a sequence by the
customizable logic is cleared, which can suddenly start operation depending on the
settings. Ensure the safety and check the operation before switching the signal.
■
Clear all customizable logic timers “CLTC” (function codes E01 to E08 Data = 81)
If the CLTC terminal function is assigned to a general-purpose input terminal and this input is turn
ON, all the general-purpose timers and counters in the customizable logic are reset. It is used to reset
and restart the system, when, for example, the timing of external sequence cannot be consistent with
internal customizable logic due to a momentary power failure.
“CLTC”
Function
OFF
Normal operation
ON
Resets all the general-purpose timers and counters in the customizable logic.
(To reactivate it, turn it OFF again.)
2-132