SVS/12
994.530 G01 02
77
Procedure
N
OTE
Check that the plug type matches the type of
connection cone.
1. Open the panel door,
remove the plinth,
detach the terminal box, if there is one, and put it
aside. Take care not to damage the secondary
cables.
2. Remove the front floor plate with the rubber grommet.
Cut a hole of the correct diameter in the grommet and
push the grommet over the cable.
3. Clean the connection cone and the plug and grease
them lightly with silicone grease.
4. Fit the plug on the connection cone in accordance with
the instructions of the manufacturer concerned. Use the
specified tightening torques.
5. Fix the cable with the cable blocks.
For wood:
drill a hole (depending on the cable diameter) in the
cable block
ensure that a 4 mm gap remains between the two
clamping halves to allow fixing of the cable
For plastic:
select the appropriate cable clamp for the cable
diameter.
6. Earth the cable sheath to the earth bar.
7. Reattach the floor plate with grommet(s), the plinth and
the terminal box, if any.
N
OTE
If plugs without an earthed exterior are used,
Eaton recommends placing an additional
interlock on the protection cover, so that the
cables are only accessible if the panel is safely
switched to the earthing position (disconnector
in the earthing position, circuit-breaker closed).
2b. Connection with two cables per phase
d
4 mm
3.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...