SVS/12
126
994.530 G01 02
9. Three-pole, short-circuit-proof back-up earth to be
installed on the 12 - 17.5 kV cable entry port of a load-
break switch or circuit-breaker panel, consisting of:
a three-phase star point with:
three earth contacts
one earthing cable
two built-in interlocks with keys
Note:
Different dimensions are available for various panels.
9.
Technical data
Rated voltage (IEC)
(kV)
12
17.5
Rated short-time withstand current for 1 sec
(kA)
20
20
Rated peak withstand current
(kA)
50
50
Earthing cable cross-section
(mm
2
)
70
70
10. Single-pole, short-circuit-proof back-up earth to be
installed on the 12 - 17.5 kV cable entry port of a load-
break switch or circuit-breaker panel, consisting of:
three earthing pins
an insulated locking plate with:
two hooked latches
two guide pins
two padlocks
one cable clamp bar
Note:
Different dimensions are available for various panels.
10.
Technical data
Rated voltage (IEC)
(kV)
12
17.5
Rated short-time withstand current for 1 sec
(kA)
20
20
Rated peak withstand current
(kA)
50
50