SVS/12
22
994.530 G01 02
2.2.6
Metering panel
The busbar system may include a metering panel (figures 1
and 2) equipped with current and voltage transformers. A
metering panel is equipped as standard with:
epoxy-resin-insulated voltage transformers The voltage
transformers are connected - on the primary side -
directly to the main busbar, in such a way as to ensure
that no spark voltages can develop at the connections
(this makes primary fuses unnecessary).
earthed or insulated primary star point
fuses or installation circuit-breakers on the secondary
side if necessary
epoxy-resin-insulated current transformers, equipped
with toroid core with secondary windings
Options
Secondary instrument compartment
Secondary equipment (protection relays, voltmeters
and ammeters)
Applications
Current measurement
Voltage measurement
kWh measurement for billing and monitoring
S
PECIAL VERSION
With universal connection for current and voltage
transformers, fitted with non-insulated copper
connections
Two panels wide
Shock hazard protected
Lock to guard against opening
Earthed metal enclosure, designed without facilities to
absorb internal arcing
Applications of special version
Customised current and voltage transformers may be
used for:
current measurement
voltage measurement
kWh measurement for billing and monitoring
Voltage
transformers
Current
transformers
1.
2.
3.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...