7. Replace the fuse in the handle.
Inserting the fuse in the 12 kV handle
W
ARNING
When fitting the fuse, do not rest the handle
against the wall or the ground, to avoid
damaging the fuse internals. Fit the fuse with the
striker pin output in the handle.
8. Slide the handle with the fuse into the installation.
Inserting the 12 kV fuse with handle
9. Close the protection cover by pushing the selector (7)
up and turning the key a quarter turn clockwise.
10. Set the disconnector to the busbar position (see
chapter 4.2.4).
11. Switch the load-break switch/fuse panel on (see
chapter 4.2.2).
Inserting the fuse in the 12 - 24 kV handle
N
OTE
On a 12 - 24 kV version, when removing the fuse
from the handle, the ring of the handle must first
be pushed backwards.
Fitting the 12 - 24 kV fuse with handle