2.2.5
Bus-section panel with load-break
switch or circuit-breaker
A bus-section panel (figure 1) includes the following
principal components as standard:
a busbar system
a disconnector
a load-break switch or a circuit-breaker
an operating mechanism
a control panel
Options
The following options are available as standard:
auxiliary contacts for load-break switch and
disconnector
electrical opening and closing of load-break switch
secondary instrument compartment
current transformers, secondary equipment
Applications
Interruption between the supply section of the electric
utility company and the user
Sectioning of an installation with different supply panels
S
PECIAL VERSION FOR A BUS
-
SECTION PANEL WITH
CIRCUIT
-
BREAKER
Circuit-breaker with integrated protection. No separate
auxiliary voltage is needed, since the current
transformers supply the power for opening.
Applications of special version
Protected bus-section panel in stations where no
auxiliary voltage is available.
1.