SVS/12
54
994.530 G01 02
P
ROCEDURE
1. Remove the floor plate with the rubber grommet.
2. Cut the cable as shown in figure 1:
L1 = 650 mm
R
EMARK
To simplify insertion of the cable cores in the
right tubes of the cable box, it is recommended
to cut the cable cores to different lengths.
3. Finish the cable as shown in figure 1:
L2 = 175 mm
d = diameter across the lead sheath
Remove the lead sheath over distance (d). Remove the sharp
edges of the lead sheath.
4. Make a hole suitable for the cable diameter in the grommet,
see figure 2. Slide the grommet over the cable, see figure 3.
5.
Remove the O-ring from the gland bush.
Saw off the underside of the gland bush resulting in a
hole whose inside diameter equals the diameter (d)
measured across the lead sheath.
6. Slide the gland bush over the lead sheath, see figure 3.
7. Solder the gland bush straight on to the lead sheath.
Preferably use soldering tin containing 35%tin and 65%
lead to keep the soldering temperature as low as
possible.
Make sure that the top of the gland bush and the end of
the lead sheath match.
8. Grease the O-ring with silicone grease or acid-free Vaseline
and slide it on to the gland bush.
9.
Slide the cable box on to the cable terminal block of the
panel and pull the cable next to the cable box so that the
bottom of the O-ring is about 15 mm higher than the
bottom of the cable box, see figure 4.
Mark the cable just above the cable clamp.
L1 = 650
L2 = 175
d
d
1.
d
2.
175
d
d
O-ring
3.
4.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...