SVS/12
994.530 G01 02
79
Required materials (figure 2)
Three insulating conduits (a) consisting of a long
part (a2) and a short part (a1)
Two bags containing three greased rubber
sleeves (b)
Three sealing plugs (c)
Three cable blocks (d)
Procedure
1. Remove the insulating conduits (a1, a2) and the
conduit support.
2. Remove the front floor plate with the rubber grommet.
Cut a hole of the correct diameter in the grommet and
push the grommet over the cable.
3. Fix the cable with the cable blocks.
For wood:
drill a hole (depending on the cable diameter) in the
cable block
ensure that a 4 mm gap remains between the two
clamping halves to allow fixing of the cable
For plastic:
select the appropriate plastic cable clamp for the
cable diameter.
4. Terminate the cable according to the manufacturer's
instructions. For the available space, see figure 1.
5. Turn the sealing plugs (c) inside out.
Carefully cut a hole in the conical part of the sealing
plugs without making any notches. The diameter of
this hole must be half the diameter of the core
insulation.
Turn the sealing plugs back to their normal position
and grease them with acid-free Vaseline.
6. Slide the sealing plugs (c) over the cable.
7. Slide a greased sleeve (b) over the long conduit (a2)
from the
87 end and slide the short conduit (a1) over
the top.
Slide the assembled conduit over the cable with the
short conduit at the bottom.
8. Fit the cable socket according to the manufacturer's
instructions.
2.
d
4 mm
3.
4.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...