SVS/12
94
994.530 G01 02
O
PTION
As an option, it is possible to have an arrangement
whereby the protection cover can only be removed if the
cable is earthed and the interlock strip is pulled out.
In this case, the load-break switch can no longer be locked
to prevent switching off in the operating position.
Procedure:
Fundamental principle:
The cable is earthed (disconnector in earthing position,
switch closed).
To open the door:
Pull the interlock strip (9) out and open the door with
the key.
To close the door:
Pull the interlock strip (9) out and close the door with
the key.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...