994.530 G01 02
10. Fix the cable in the cable clamp at the marked position,
see figures 6 and 7.
Tighten the cable block. Check that the cable lies straight
under the connection. Remove any spacer from the
support of the cable block.
11. Seal the openings of the cable box to prevent intrusion
of dirt.
12.
Cut the cable cores 2 to 3 mm below the cast
resin insulation (figure 7).
Remove the paper insulation from the cable cores
over a distance of 30 mm.
13.
Check that the O-rings are fitted over the cast
resin insulation, see figure 8.
Apply some cable grease to the cast resin
insulation.
6.
7.
8.
Cable terminal block