SVS/12
28
994.530 G01 02
2.4.2
Interlocks, 1250 A panels
Definitions
Panel in the "operating position" means:
the disconnector is in the busbar position and the
circuit-breaker is closed
Panel in the "earthing position" means:
the disconnector is in the earthing position and the
circuit-breaker is closed
Panel in the "intermediate position" means:
the disconnector is in the busbar or earthing position
and the circuit-breaker is open.
Disconnector
The disconnector can only be operated if the circuit-
breaker is open.
Circuit-breaker panel
The circuit-breaker can only be closed if the
disconnector is fully in the busbar position or fully in the
earthing position.
A panel is provided with a padlock to prevent the
circuit-breaker from being opened in the earthing
position
As an option, an interlock can be provided on the
access door of the cable compartment:
This means that the door can only be opened in the
earthing position.
Bus-section panel
On a bus-section panel, the circuit-breaker can be
closed if one of the disconnectors is in the earthing
position. For this reason the main busbar can be
earthed.
The circuit-breaker can be locked with a padlock.
Metering panel
A padlock can be provided on the access door of a
metering panel.
2.4.3
Safety
System-specific safety instructions appear in this manual
as instructions (such as warnings, life hazard etc.) before
or within the relevant operation in the step-by-step
procedures.
The procedures describe what the user may do:
The user must follow the procedures closely and should
only use the accessories supplied.
The user must observe the safety instructions indicated
before the relevant procedures or operations.
No other activities whatsoever are permitted.
When panels are open, the user is responsible for
safety during work on the installation.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...