SVS/12
994.530 G01 02
55
10. Remove the cable box from the cable terminal block.
11. Slide the cable box as far as possible on to the cable. Make
sure the paper insulation of the cable cores does not get
damaged.
12. Fix the cable in the cable clamp at the marked position, see
figures 5 and 6.
Move the distance piece until the centre of the cable is
exactly in line with the centre of the cable box. Firmly tighten
the cable clamp.
13. For cables with an aluminium core:
If the crimp cable clamps have been fitted, fix them in
accordance with the instructions.
In this case, skip step 12.
14. Depending on the core diameter, follow the procedure
described in:
chapter 3.3.4, steps 9-14
chapter 3.3.5, steps 2-8
15. Fit the hose clip to the gland bush at the level of the O-ring,
see figure 7.
16. Secure the floor plate. Place the grommet in the floor plate.
17. Fill the cable box with grease (see chapter 3.3.8).
5.
6.
7.
Summary of Contents for SVS/12