Procedure
1. Attach the cable box to the cable, following the procedure
described in chapter 3.3.4, steps 1-13.
2. Fit the connecting pieces to the connection pins using one of
the washers:
Tighten the hexagon socket head screws (torque
15 Nm). Make sure that the screws are positioned
straight forward in all three phases.
3. Slide the other washers as far as possible on to the
connecting pieces and provisionally tighten the hexagon
socket head screws.
4. Seal the openings of the cable box to prevent intrusion of
dirt.
5. Shorten the cable cores so that all three of them fit into the
recesses in the connecting pieces.
6. Position the cable cores in the recesses in the connecting
pieces. Fit the glands on to the core ends in the recesses in
the connecting pieces and slide the lower washers along the
glands (figure 2).
Tighten the hexagon socket head screws (torque
15 Nm). Make sure that the screws are positioned
straight forward in all three phases.
After a time, re-tighten the hexagon socket head screw
of the cable core clamps.
1.
2.
washers
connecting
pieces
washer
washer
gland
connecting piece