SVS/12
42
994.530 G01 02
Procedure
Terminating cables (for non-Eaton cables)
1. Check on the basis of tables 1 and 2 that you have the
correct parts to hand.
2. Terminate the cable cores to the correct length, as
shown in figure 2.
The cable core insulation must be perfectly
smooth on the outside. The presence of
grooves and ridges can lead to insulation that
is "not completely electrically sealed".
3. Using a suitable pressing tool (see table 2), fix the
cable core bushes on the cable cores; the position and
number of clamping rings are marked with a groove on
the cable core bushes.
Connecting cables (for Eaton and non-Eaton cables)
4. Lead the three cables into the installation via the
underside (from the cellar).
5. Make a hole suitable for the cable diameter in the
grommet. Slide the grommet over the cable.
6. Grease the cable at the location of the primary cable
insulation and place the 3 cable sleeves over the cable
core bushes.
N
OTE
Use the correct type of grease:
for grey rubber sleeves: silicone grease.
7. Insert the cable with the sleeve carefully from
underneath into the cable connection (figure 5). Make
sure the sleeves are not pushed back.
8. Push the cable inside from underneath, until the cable
core bush meets the contact face inside the connection.
2.
3.
4.
5.
Crimping direction
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...