SVS/12
72
994.530 G01 02
10. Seal the openings of the cable box to prevent intrusion
of dirt.
11. Shorten the cable cores so that all three of them fit into
the recesses in the connecting pieces.
12. Insert the rubber sleeves (b) previously greaseed with
silicone grease upwards into the feed opening of the
insulating conduits (a) and slide the conduits over the
cores, see figure 7.
13.
Position the cable cores in the recesses in the
connecting pieces. Fit the glands on to the core
ends in the recesses in the connecting pieces and
slide the lower washers along the glands, see
figure 8.
Tighten the hexagon socket head screws (approx.
15 Nm). Make sure that the screws are positioned
straight forward in all three phases.
Re-tighten the hexagon socket head screws of the
cable core clamps after some time.
7.
8.
washer
gland
connecting piece
washer
connecting piece
washer
gland
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...