SVS/12
994.530 G01 02
37
3.3 Cable connection on 630 A panels
The safety regulations must be observed when connecting cables (see chapter 1.3).
Different cable connections are available with SVS/12 switchgear. The following is an overview of connections on 630 A panels.
See chapter 3.4 for connections on 1250 A panels.
12 kV
12 - 17,5 - 24 kV
LOAD SWITCH and POWER SWITCH PANELS
12 kV
Panel equipped
with:
connection block
with locked cable
access ports for
Magnefix-
connections
Panel equipped
with:
cones according to
EN50181:
types C and D
Panel equipped
with:
connection block
with locked cable
access ports for
cable socket con-
nections
Grease filled end seals
for paper lead cable
maximum 70 mm
2
Cu
See chapter 3.3.4
maximum 150 mm
2
Cu
maximum 120 mm
2
Al
See chapter 3.3.4 en 3.3.5
maximum 240 mm
2
Cu or Al
with soldering gland
See chapter 3.3.6
maximum 240 mm
2
Cu or
Al with synthetic inlet tube
See chapter 3.3.7
Dry end seals for synthe-
tic cable
maximum 240 mm
2
Cu or Al
See chapter 3.3.10
Plug connection with
T-plugs with screw
connection for synthetic
cables
Type C:
maximum
240 mm
2
Cu or Al
Type D:
maximum
630 mm
2
Cu or Al
See chapter 3.3.1
1 cable
per phase
2 cables
per pha-
se
Dry end seal for
synthetic cables
max 630 mm
2
CU or Al
See chapter 3.4.2
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...