SVS/12
994.530 G01 02
99
4.3 Earthing of cables
4.3.1
Earthing of the cable via the load-break
switch or circuit-breaker, 630 A and
1250 A panels
1. Turn the load-break switch or circuit-breaker
off
(see
2. Set the disconnector to the
earthing position
(see
3. Check the operation of the voltage indicator with the
tester (see appendix 9.2).
4. Using the voltage indicator, check that the earthing
cable is not live (see appendix 9.2).
5. Turn the load-break switch or circuit-break
on
(see
6. The cable is now earthed via the load-break switch or
circuit-breaker.
7. Lock the installation where applicable with a padlock
(see chapter 4.2.7)